Plan Review Notes For Permit 04080311 |
Permit Number |
04080311 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-13 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE PROVIDE 2(TWO) SETS OF PLANS | | FOR REVIEW. | | | | 2} ALL PLANS SUBMITTED BY AN ARCHITECT | | MUST BE SIGNED AND SEALED BY THE | | DESIGNER PER 481 FS.& 61G1-16.003 FAC. | | | | 3} THE GENERAL LIGHTING LOAD MUST BE CAL | | CULATED @ 3 1/2 VA PER 220.3(A). | | | | 4} THE SIGN LIGHTING CALCULATION MUST CO | | MPLY WITH 220.3(B)(6), 1200VA. | | | | 5} THE TRACK LIGHTING LOAD MUST BE CALCU | | LATED @ 1200VA. PER 220.12(B). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|