2004-08-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE 2(TWO) SETS OF PLANS
 FOR REVIEW.
  
 2} ALL PLANS SUBMITTED BY AN ARCHITECT
 MUST BE SIGNED AND SEALED BY THE
 DESIGNER PER 481 FS.& 61G1-16.003 FAC.
  
 3} THE GENERAL LIGHTING LOAD MUST BE CAL
 CULATED @ 3 1/2 VA PER 220.3(A).
  
 4} THE SIGN LIGHTING CALCULATION MUST CO
 MPLY WITH 220.3(B)(6), 1200VA.
  
 5} THE TRACK LIGHTING LOAD MUST BE CALCU
 LATED @ 1200VA. PER 220.12(B).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW