Plan Review Notes
Plan Review Notes For Permit 04080236
Permit Number 04080236
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE PROVIDE A RISER DIAGRAM PER
 215.5.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 3} PLEASE VERIFY THAT THE AIR HANDLER
 HAS ONLY 10K OF HEAT FOR A 1100 SQ FT.
 RESIDENCE. ALSO INDICATE THE COMPRESSOR
 LOAD.
  
 4} PROVIDE A PANEL SCHEDULE SO THAT BC
 BREAKER & WIRE SIZES ARE PER CODE.
  
 5} PLEASE LABEL ROOMS.
  
 6} SHOW STAIR LIGHTING PER 210.70.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026