Plan Review Notes For Permit 04080236 |
Permit Number |
04080236 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-12 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE PROVIDE A RISER DIAGRAM PER | | 215.5. | | | | 2} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | CURRENT PER 110.9. | | | | 3} PLEASE VERIFY THAT THE AIR HANDLER | | HAS ONLY 10K OF HEAT FOR A 1100 SQ FT. | | RESIDENCE. ALSO INDICATE THE COMPRESSOR | | LOAD. | | | | 4} PROVIDE A PANEL SCHEDULE SO THAT BC | | BREAKER & WIRE SIZES ARE PER CODE. | | | | 5} PLEASE LABEL ROOMS. | | | | 6} SHOW STAIR LIGHTING PER 210.70. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|