2005-04-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) GAS WATER HEATER TIE DOWN DETAIL
 SHOWS THE CONCRETE PAD AS 3", WHEREAS
 THE TYPICAL SLAB DETAIL ON THE GENERAL
 NOTES SHEET SHOW A 4" THICK SLAB AS IS
 REQUIRED. PLEASE CORRELATE DETAILS.
 SECTION 104.2.1.
 2) SPECIFICATION SHEET SHOWS THE SHEER
 DECENT/LION HEAD RETURNS ON THE SIDE OF
 THE POOL, BUT THE LAYOUT SHEET SHOWS
 THESE RETURNS AT THE END OF THE POOL.
 PLEASE CLARIFY AND CORRELATE SHEETS.
 SECTION 104.2.1.
 3) TWO SETS OF PLANS ARE REQUIRED TO BE
 SUBMITTED WITH APPLICATION FOR PERMIT.
 LOOSE SHEETS ARE NOT SETS OF PLANS.
 SECTION 104.2.1.
  