Plan Review Notes
Plan Review Notes For Permit 04080211
Permit Number 04080211
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-22 00:00:00DENIED
 REFERENCE: FBC-424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
  
 1) THE FOLLOWING INFORMATION IS REQUIRED
 ON THE PLANS EITHER IN THE FORM OF
 NOTES, DRAWINGS, OR SUBMITTALS:
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK. - NO
 VACUUM LINE IS SHOWN ON THE POOL LAYOUT
 SHEET, BUT A VACUUM LINE IS INDICATED ON
 THE PIPING SCHEMATIC. PLEASE CLAIRFY AND
 CORRELATE PIPING SCHEMATIC WITH POOL
 LAYOUT. (GIVE DETAIL, SUBMITTAL OR ADD
 TO NOTES) SECTION 104.2.1.
 3) FBC-2001424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)- UNABLE TO READ MINIMUM
 SEPARATION BETWEEN MAIN DRAINS ON THE
 PLANS. PLEASE INDICATE 3 FT. SECTION
 104.2.1.
 4) SHEET WITH PIPING SCHEMATIC HAS A
 NOTE THAT STATES "HEATER IS EXCEMPT FROM
 STATE ENERGY CODE AS HEAT SOURCE IS AND,
 IS 90% EFICIENT". THIS IS NOT THE CASE
 WITH GAS POOL HEATERS AND SHALL BE
 DELETED FROM THE PLANS.
 5) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 6) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUF. CUT SHEETS - SUBMITTAL)
 7) FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED. (ADD TO NOTES)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]