Plan Review Notes
Plan Review Notes For Permit 04080209
Permit Number 04080209
Review Stop P
Sequence Number 3
Notes
Date Text
2004-11-02 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING
 POOLS
 FBC-2001 CHAPTER 1
  
 FROM PREVIOUS REVIEW:
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 HEATERS SHALL BEAR THE LABEL OF A REC-
 OGNIZED TESTING AGENCY. MANUF. SHEETS
 REQUIRED. (SUBMITTAL)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. MANUF CUT SHEETS (SUBMITTAL)
 6) FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE
 PLANS AND PERMIT REQUIRED.
 8) POOL PIPING LAYOUT SHOWS MAIN DRAIN
 LINE CONNECTING TO ONE MAIN DRAIN,
 WHERE
 AS PIPING SCHEMATIC INDICATES
 CONNECTION
 AT THE CENTER OF THE MAIN DRAINS. (ALSO
 SEE APPROVED SWIMMING POOL & SPA DUAL
 MAIN DRAIN ATMOSPHERIC VENT ARRANGEMENT
 DETAIL). PER SECTION 424.2.6.6.4 THESE
 SUCTION INLETS SHALL BE PLUMBED SUCH
 THAT WATER IS DRAWN THROUGH THEM SIM-
 ULTANEOUSLY. CORRECT THE PIPING LAYOUT
 TO REFLECT THE EQUIPMENT SCHEMATIC AND
 DRAIN/VENT ARRANGEMENT COMPLIANT WITH
 SECTION 424.2.6.6.
 A) PLEASE ADJUST YOUR NOTES, DETAILS,
 OR SUBMITTALS TO REFLECT THE ABOVE
 INFORMATION REQUIRED FOR PLAN REVIEW.
 ***NEW COMMENT
 1B) POOL PIPING SCHEMATIC HAS HAND
 DRAWN CHANGES. THIS IS NOT APPROVED.
 SUBMIT NEW PIPING SCHEMATIC WITH ALL
 APPROVED CHANGES.
 2B) REMOVE ALL VOIDED SHEETS, SUBMIT
 2 SETS OF PLANS FOR REVIEW AND ONE SET
 OF VOIDED SHEETS FOR COMPAIRSON.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]