2004-08-11 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| FBC-2001 CHAPTER 1 |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| PROTECTION FOR SUCTION INLETS. (DETAIL) |
| 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| 3) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| MENT AVOIDANCE. (DETAIL) |
| 4) FBC-2001 424.2.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. MANUFACTURE |
| SHEETS REQUIRED. (SUBMITTAL) |
| 5) FBC-2001 424.2.14.2 WATER RETENTION, |
| PROVIDE A POSITIVE MEANS OF RETAINING |
| WATER IN THE HEATER WHEN PUMP IS SHUT |
| OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| 6) FBC02001 424.2.15 GAS PIPING SHALL |
| COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| AND PERMIT REQUIRED. |
| 7) POOL EQUIP SCHEDULE & PIPING SCHEMAT- |
| IC INDICATE A VACUUM CLEANER LINE, BUT |
| POOL PIPING LAYOUT DOES NOT REFLECT THIS |
| ITEM. PLEASE CORRELATE PLANS. SECTION |
| 104.2.1. |
| 8) POOL PIPING LAYOUT SHOWS MAIN DRAIN |
| LINE CONNECTING TO ONE MAIN DRAIN, WHERE |
| AS PIPING SCHEMATIC INDICATES CONNECTION |
| AT THE CENTER OF THE MAIN DRAINS. PER |
| SECTION 424.2.6.6.4 THESE SUCTION INLETS |
| SHALL BE PLUMBED SUCH THAT WATER IS |
| DRAWN THROUGH THEM SIMULTANEOUSLY. CORR- |
| ECT THE PIPING LAYOUT TO REFLECT THE |
| EQUIPMENT SCHEMATIC. SECTION 1104.2.1. |
| 9) EQUIPMENT PIPING SCHEMATIC CALLS OUT |
| THE POOL HEATER AS A 109K HEAT PUMP, BUT |
| EQUIPMENT SPECIFICATIONS INDICATE A 400K |
| NATURAL GAS POOL HEATER. CORRELATE PLANS |
| SECTION 104.2.1. |
| 10) PIPING SCHEMATIC NOTES STATE: HEATER |
| IS EXEMPT FROM STATE ENERGY CODE AS A |
| HEAT SOURCE IS 90% EFFECIENT. GAS HEAT- |
| ERS ARE NOT EXEMPT. DELETE NOTE. SECTION |
| 104.2.1. |
| 11) ANTI ENTRAPMENT PIPING DESIGN NOTES |
| #3. ENTRAPMENT DEVICES SHALL, (NOT MAY), |
| COMPLY WITH ANSI/ASME A112.19.8.M. SECT- |
| ION 424.2.6.6.2. |
| |
| REVIEW BY KEN STEVENS |