Plan Review Notes
Plan Review Notes For Permit 04080209
Permit Number 04080209
Review Stop P
Sequence Number 1
Notes
Date Text
2004-08-11 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
 FBC-2001 CHAPTER 1
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 3) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5) FBC-2001 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 6) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 7) POOL EQUIP SCHEDULE & PIPING SCHEMAT-
 IC INDICATE A VACUUM CLEANER LINE, BUT
 POOL PIPING LAYOUT DOES NOT REFLECT THIS
 ITEM. PLEASE CORRELATE PLANS. SECTION
 104.2.1.
 8) POOL PIPING LAYOUT SHOWS MAIN DRAIN
 LINE CONNECTING TO ONE MAIN DRAIN, WHERE
 AS PIPING SCHEMATIC INDICATES CONNECTION
 AT THE CENTER OF THE MAIN DRAINS. PER
 SECTION 424.2.6.6.4 THESE SUCTION INLETS
 SHALL BE PLUMBED SUCH THAT WATER IS
 DRAWN THROUGH THEM SIMULTANEOUSLY. CORR-
 ECT THE PIPING LAYOUT TO REFLECT THE
 EQUIPMENT SCHEMATIC. SECTION 1104.2.1.
 9) EQUIPMENT PIPING SCHEMATIC CALLS OUT
 THE POOL HEATER AS A 109K HEAT PUMP, BUT
 EQUIPMENT SPECIFICATIONS INDICATE A 400K
 NATURAL GAS POOL HEATER. CORRELATE PLANS
 SECTION 104.2.1.
 10) PIPING SCHEMATIC NOTES STATE: HEATER
 IS EXEMPT FROM STATE ENERGY CODE AS A
 HEAT SOURCE IS 90% EFFECIENT. GAS HEAT-
 ERS ARE NOT EXEMPT. DELETE NOTE. SECTION
 104.2.1.
 11) ANTI ENTRAPMENT PIPING DESIGN NOTES
 #3. ENTRAPMENT DEVICES SHALL, (NOT MAY),
 COMPLY WITH ANSI/ASME A112.19.8.M. SECT-
 ION 424.2.6.6.2.
  
 REVIEW BY KEN STEVENS