Plan Review Notes
Plan Review Notes For Permit 04080179
Permit Number 04080179
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-21 00:00:00********UNSAT *********
  
 1)NOTE:PLEASE SHOW METER/MAIN ON PLAN
 WHICH IS LOCATED OUTSIDE WHERE OLD METER
 IS SHOWN?
 215.5
  
 2)NOTE: PLEASE SEE NOW THAT A METER/MAIN
 IS INSTALLED, AN EQUIPMENT GROUNDING
 CONDUCTOR IS REQUIRED TO BE INSTALLED
 FROM METER/MAIN TO PANEL "B".
 250.110,250.24, 250.122
  
 3)NOTE: PLEASE SHOW METER MAIN WITH FEED
 THRU LUGS, OR LIST OCP ON METER MAIN
 PANEL SCHEDULE "A".
  
 4)NOTE: PLEASE VERIFY PANEL "B" IS STILL
 SHOWN AS MCB, EVEN NOW THAT A MAIN IS
 INSTALLED OUTSIDE. PLEASE SEE THIS IS
 PERMITTED, HOWEVER NOT REQUIRED.
 THIS IS ONLY A NOTE: IF SHOWN AS MCB,
 THEN A MCB WILL BE REQUIRED PER PLANS.
  
 5)NOTE: PLEASE IDENTIFY NEW RECEPTS
 ADDED TO REAR PORCH AND GARAGE AS GFI.
 210.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  