Plan Review Notes For Permit 04080179 |
Permit Number |
04080179 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-04-21 00:00:00 | ********UNSAT ********* | | | | 1)NOTE:PLEASE SHOW METER/MAIN ON PLAN | | WHICH IS LOCATED OUTSIDE WHERE OLD METER | | IS SHOWN? | | 215.5 | | | | 2)NOTE: PLEASE SEE NOW THAT A METER/MAIN | | IS INSTALLED, AN EQUIPMENT GROUNDING | | CONDUCTOR IS REQUIRED TO BE INSTALLED | | FROM METER/MAIN TO PANEL "B". | | 250.110,250.24, 250.122 | | | | 3)NOTE: PLEASE SHOW METER MAIN WITH FEED | | THRU LUGS, OR LIST OCP ON METER MAIN | | PANEL SCHEDULE "A". | | | | 4)NOTE: PLEASE VERIFY PANEL "B" IS STILL | | SHOWN AS MCB, EVEN NOW THAT A MAIN IS | | INSTALLED OUTSIDE. PLEASE SEE THIS IS | | PERMITTED, HOWEVER NOT REQUIRED. | | THIS IS ONLY A NOTE: IF SHOWN AS MCB, | | THEN A MCB WILL BE REQUIRED PER PLANS. | | | | 5)NOTE: PLEASE IDENTIFY NEW RECEPTS | | ADDED TO REAR PORCH AND GARAGE AS GFI. | | 210.8 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | |
|