Plan Review Notes For Permit 04071424 |
Permit Number |
04071424 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-05-03 00:00:00 | **** UNSAT ***** | | | | PLEASE SEE PLANS APPEAR TO BE FOR | | FINALS. | | PLEASE MAKE THE CORRECTIONS LISTED | | BELOW. | | | | | | 1)NOTE: PLEASE SEE PLANS INDUCATE TWO | | MAIN DISCONNECTS OUTSIDE NEXT TO METER, | | HOWEVER RISER DOES NOT SHOW ANY MAINS. | | PLEASE CORRELATE. | | 215.5 | | | | 2)NOTE: PLEASE SEE DRYER IS SHOWN WITH | | 5KW LOAD ON A 1-P20A CIRCUIT. PLANS | | INDICATE DRYER AS GAS? | | | | 3)NOTE: PLEASE VERIFY #OF #6 CONDUCTORS | | SHOWN FOR OVEN. PLEASE SEE COOKTOP IS | | SHOWN WITH 7.6KW ON A 20A 1POLE CIRCUIT. | | IF SHOWN WITH 4-#6'S THEN THESE WOULD BE | | REQUIRED. | | | | PLEASE VERIFY. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|