Plan Review Notes For Permit 04071423 |
Permit Number |
04071423 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-13 00:00:00 | 1) DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2) DEBRIS SHALL BE REMOVED FROM | | THE SITE DAILY. | | | | 3) ONLY 30" PROVIDED FOR EXITING | | IN EXISTING HALLWAY 0737. 44" REQUIRED. | | PLEASE REVISE AS NECESSARY. | | | | 4) NO 04 ON PAGE DE-101. | | | | 5) FUEL POWERED EQUIPMENT USED MUST | | BE PROVIDED WITH PROPER VENTILATION | | TO PREVENT THE ACCUMULATION OF | | CARBON MONOXIDE. | | | | 6) PLEASE ILLUSTRATE ALL ILLUMINATED | | EXIT SIGNS AND EMERGENCY LIGHTS. | | | | 7) ON PAGE E-101, ONLY ONE FIRE ALARM | | HORN STROBE COULD BE LOCATED ON | | THE PLANS. PLEASE ADVISE. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|