2004-08-05 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04071423 |
| ADD: 625 N FLAGLER DR# 700 |
| CONT: SGRA. LOURDES GURREA |
| TEL: (954) 961-6806 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| PLANS DO NOT INDICATE WHAT THE RATING |
| IS ON THE FRONT ENTRY DOORS WILL BE, IT |
| IS IN A HIGHLIGHTED AREA WORK TO BE |
| COMPLETED? |
| |
| 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 4) SHEET A-101 SEE NEW OFFICE 0712A, |
| IN FRONT OF THIS NEW OFFICE THERE IS A |
| EXISTING COLUMN. WITH THE CREATION OF |
| THE NEW OFFICE IT APPEARS TO BE LESS |
| THAN 30" CLEAR.MEANS OF EGRESS REQUIRES |
| 44", 36" FOR CORRIDORS WITH AN OCCUPANT |
| LOAD LESS THAN 50. |
| |
| 5) PROVIDE THE MINIMUM BUILDING TYPE? |
| 7 STORIES SHOULD REQUIRE TYPE II , |
| 609.2.1 PARTITIONS AND BACKING ARE TO BE |
| NONCOMBUSTIBLE. |
| |
| 8)11-4.1.6(2) DUTY TO PROVIDE AN |
| ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| AREAS SHALL BE DEEMED DISPROPORTIONATE |
| TO THE OVERALL ALTERATION WHEN THE COST |
| EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| TION TO THE PRIMARY FUNCTION AREA. |
| (A)(I) AN ACCESSIBLE ENTRANCE |
| (II) AN ACCESSIBLE ROUTE |
| (III) AT LEAST ONE ACCESSIBLE REST- |
| ROOM FOR EACH SEX OR A SINGLE |
| UNISEX RESTROOM |
| (IIII) ACCESSIBLE TELEPHONE |
| (IV) ELEMENTS SUCH AS PARKING, STOR- |
| AGE OR ALARMS. |
| OFFICE 708, THE ENTRY DOES NOT MEET THE |
| REQUIRED 18" CLEAR ON THE PULL SIDE OF |
| THE OFFICE DOORWAY. |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| 9)DOES THIS BUILDING HAVE FIRE SPRINKLER |
| SYSTEM? IF SO PROVIDE UPDATES TO THIS |
| FLOOR. |
| |