Plan Review Notes
Plan Review Notes For Permit 04071423
Permit Number 04071423
Review Stop B
Sequence Number 1
Notes
Date Text
2004-08-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071423
 ADD: 625 N FLAGLER DR# 700
 CONT: SGRA. LOURDES GURREA
 TEL: (954) 961-6806
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 PLANS DO NOT INDICATE WHAT THE RATING
 IS ON THE FRONT ENTRY DOORS WILL BE, IT
 IS IN A HIGHLIGHTED AREA WORK TO BE
 COMPLETED?
  
 3)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 4) SHEET A-101 SEE NEW OFFICE 0712A,
 IN FRONT OF THIS NEW OFFICE THERE IS A
 EXISTING COLUMN. WITH THE CREATION OF
 THE NEW OFFICE IT APPEARS TO BE LESS
 THAN 30" CLEAR.MEANS OF EGRESS REQUIRES
 44", 36" FOR CORRIDORS WITH AN OCCUPANT
 LOAD LESS THAN 50.
  
 5) PROVIDE THE MINIMUM BUILDING TYPE?
 7 STORIES SHOULD REQUIRE TYPE II ,
 609.2.1 PARTITIONS AND BACKING ARE TO BE
 NONCOMBUSTIBLE.
  
 8)11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 OFFICE 708, THE ENTRY DOES NOT MEET THE
 REQUIRED 18" CLEAR ON THE PULL SIDE OF
 THE OFFICE DOORWAY.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 9)DOES THIS BUILDING HAVE FIRE SPRINKLER
 SYSTEM? IF SO PROVIDE UPDATES TO THIS
 FLOOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026