2004-08-11 00:00:00**********DENIED************************
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENT
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 APPROVAL OF THESE PLANS OR PROOF OF
 APPLICATION TO UL.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 4) ALL DUCT SMOKE DETECTORS SHALL SEND
 AND PUT THE SYSTEM IN GENERAL FIRE ALARM
 MODE IN THE CITY OF WEST PALM BEACH NOT
 A SUPERVISORY SIGNAL.
  