2004-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) HAND DRAWN INFORMATION IS NOT PERMIT-
 TED ON SIGNED/SEALED DRAWINGS. FS 481.
 2) SUBMIT A WATER RISER DIAGRAM SHOWING
 POINT OF CONNECTION, PIPE SIZES, AND
 LOCATION OF REQUIRED WATER HAMMER ARRES-
 TORS, (AT WASH MACHINE).
 3) SANITARY RISER DIAGRAM SHOWS AIR AD-
 MITTENCE VALVES FOR BRANCH LINE TO W/M &
 SINK, BUT NOTE ON PLANS STATES, "CONNECT
 2" VENT TO EXISTING VENT @ WATER COOLER"
 PLEASE CORRELATE.
  