Plan Review Notes For Permit 04071378 |
Permit Number |
04071378 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-19 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) HAND DRAWN INFORMATION IS NOT PERMIT- | | TED ON SIGNED/SEALED DRAWINGS. FS 481. | | 2) SUBMIT A WATER RISER DIAGRAM SHOWING | | POINT OF CONNECTION, PIPE SIZES, AND | | LOCATION OF REQUIRED WATER HAMMER ARRES- | | TORS, (AT WASH MACHINE). | | 3) SANITARY RISER DIAGRAM SHOWS AIR AD- | | MITTENCE VALVES FOR BRANCH LINE TO W/M & | | SINK, BUT NOTE ON PLANS STATES, "CONNECT | | 2" VENT TO EXISTING VENT @ WATER COOLER" | | PLEASE CORRELATE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|