Plan Review Notes
Plan Review Notes For Permit 04071368
Permit Number 04071368
Review Stop P
Sequence Number 2
Notes
Date Text
2004-11-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
  
 A) COMMENT FROM PREVIOUS REVIEW HAS NOT
 BEEN ADDRESSED.
 2) STAFF SINK SHALL COMPLY WITH SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING REQUIREMENTS. SHOW:
 A) HEIGHT 4.24.2
 B) KNEE CLEARANCE 4.24.3
 C) SINK DEPTH 4.24.4
 D) CLEAR FLOOR SPACE - SHALL BE PROVIDED
 IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH, AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK. (FIG 32).
 E) EXPOSED PIPES AND SURFACES. 4.24.6
 - RESPONSE STATES "REFER TO
 ARCHITECTURAL PLANS", BUT UNABLE TO
 LOCATE DETAIL FOR SINK.
 *****NEW COMMENT*****
 B) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH 11-4.15
  
 AND ALL SUBSECTIONS. SHOW:
 1) SPOUT HEIGHT 4.15.2
 2) CLEARANCES 4.15.5 WITH CLEAR FLOOR
 SPACE.
 3) ACCESSIBILITY FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
 11-4.1.3(10)(A).
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]