Plan Review Notes For Permit 04071368 |
Permit Number |
04071368 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-20 00:00:00 | DENIED: | | 1. PLEASE PROVIDE OUTSIDE AIR CALCS PER | | 2001 FBC(M) 403.3. | | | | 2.NO COMBUSTIBLES ABOVE THE CEILING | | IN THE RETURN AIR PLENUM PER 2001 FBC(M) | | 602.2.1. | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | REQUIRED PER 2001 FBC(M) 606.2.2, ALSO | | NOTIFICATION TO ALARM/STROBE IN NORMALLY | | OCCUPIED AREAS. | | | | 4.PLANS ARE REQUIRED TO SIGNED, SEALED | | AND DATED BY THE ENGINEER IN ACCORDANCE | | WITH FS 471.025 & FAC 61G15-23.002. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|