Plan Review Notes
Plan Review Notes For Permit 04071368
Permit Number 04071368
Review Stop M
Sequence Number 1
Notes
Date Text
2004-08-20 00:00:00DENIED:
 1. PLEASE PROVIDE OUTSIDE AIR CALCS PER
 2001 FBC(M) 403.3.
  
 2.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM PER 2001 FBC(M)
 602.2.1.
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 REQUIRED PER 2001 FBC(M) 606.2.2, ALSO
 NOTIFICATION TO ALARM/STROBE IN NORMALLY
 OCCUPIED AREAS.
  
 4.PLANS ARE REQUIRED TO SIGNED, SEALED
 AND DATED BY THE ENGINEER IN ACCORDANCE
 WITH FS 471.025 & FAC 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.