Plan Review Notes For Permit 04071350 |
Permit Number |
04071350 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-09-22 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | SHEET "A3" WAS NOT SUBMITTD FOR REVIEW | | PREVIOUSLY. SINCE THIS SHEET CONTAINS | | EXTENSIVE ELECTRICAL WORK NOT IN THE | | ORIGINAL SCOPE PLEASE PROVIDE THE | | FOLLOWING. | | | | 1) INDICATE THE SIZE OF THE EXISTING | | SERVICE. INCLUDE A RISER DIAGRAM. | | | | 2) PROVIDE A PANEL SCHEDULE SHOWING ALL | | ADDED OR EXTENDED CIRCUITS, INCLUDING | | CONDUCTOR AND OVERCURRENT PROTECTION | | SIZES OF SAME. BE SURE TO LIST ALL | | ADDED EQUIPMENT CIRCUITS AS WELL AS | | GENERAL CIRCUITING. | | | | 3) ALL KITCHEN COUNTERTOP RECEPTACLES | | MUST COMPLY WITH 210.8(A)(6), INDICATE | | SAME ON DRAWING.(GFI). | | | | 4} PLEASE CLARIFY THE RECEPTACLE SHOWN | | AWAY FROM THE WALL IN THE MASTER | | BEDROOM. IS THIS A FLOOR RECEPTALCLE OR | | WALL MOUNTED ? SEE 210.52(A)(3) IF | | FLOOR. | | | | 5) PLEASE INCREASE THE VALUE OF THE | | PROPOSD WORK TO INCLUDE ADDED SCOPE ON | | SHEET A3. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|