Plan Review Notes For Permit 04071290 |
Permit Number |
04071290 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-10-21 00:00:00 | ******** UNSAT ********* | | | | 1)NOTE: PLEASE SEE LOAD ON PANEL "C" | | EXCEEDS FEEDER AND OCP FOR PANEL. | | PLEASE ALSO INDICATE ALL CONTINUOUS | | LOADS AT 125%. | | 215.3,230.42 ETC. | | PLEASE REVISE 240.4,310.16,310.15B6 | | | | 2)NOTE: PLEASE SEE BOTH PANELS "A" AND | | "B" INDICATE BEING MLO. | | PLEASE SEE RISER SHOWS THESE AS MCB. | | PLEASE CORRELATE AND INDICATE MCB'S AS | | REQIRED 230.70 | | | | 3)NOTE: PLEASE SEE GROUNDING ELECTRODE | | IS NOW SHOWN GOING TO SLAB, HOWEVER THIS | | SHOULD BE NOTED AS FOOTER STEEL. 250.50 | | | | 4)NOTE: PLEASE CORRELATE RECESSED LTS ON | | LOAD CALCULATIONS AND THE NUMBER OF LTS | | SHOWN ON PLANS. | | 215.5,220.3 | | | | | | ** NOTE ALL SD'S ARE TO BE INSTALLED | | WITH IN THE HIGHEST POINT OF A FLAT | | CEILING. | | PLEASE BE SURE TO VERIFY INSTALLATION IN | | FIELD. | | NFPA-72 8-1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|