2005-04-20 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SEE PANEL "C" IS MISSING
 FROM PLANS. PLEASE SHOW LOCATION OF
 PANEL "C" ON PLANS.
 215.5
  
 2)NOTE: PLEASE SEE RECEPT FOR WHIRLPOOL
 TUB NOT SHOWN AS GFI/GFI PROTECTED.
 680.24
  
 3)NOTE: PLEASE SEE MISSING GFI ON
 POWDER/BATHRM. 210.52D, 210.8
  
 4)NOTE: PLEASE SEE NOTE #2 ON GEN NOTES
 MENTIONS SD'S ON KIT/BATH LIGHTING
 CIRCUITS, HOWEVER THESE ARE REQUIRED TO
 HAVE ARC FAULT PROTECTION PER 210.12
 2002 NEC.
 IF ON KIT/BATH LIGHTING CIRCUIT(S),
 THESE WOULD ALSO BE REQUIRED TO BE AFCI.
  
 PLEASE KNOW, SINCE PLANS ARE IN FOR
 FINAL, ALL ITEMS MUST BE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW