Plan Review Notes For Permit 04071255 |
Permit Number |
04071255 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-05 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | CURRENT PER 110.9. | | | | 2} PLEASE SHOW CONDUIT SIZE AND TYPE ON | | RISER. | | | | 3} PLEASE SUBMIT A PANEL SCHEDULE WITH | | WIRE AND BREAKER SIZES SO BC COMPLIANCE | | CAN BE DETERMINED.(IG: 210.12, | | 210.11(C)(3), 210.52(B), ETC.) | | | | 4} PLEASE SHOW OUTLET SPACING PER | | 210.52. 2',6',12' RULES. | | | | 5} PLEASE SEE RECEPTS SERVING | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | SEC'S 1,2,3,4 AND 5. | | | | 6} SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | SEE 8-1.4.2 NFPA-72 FOR ADDITIONAL | | SPACING ISSUES, 1999 ED. | | | | 7} THE RANGE FEEDER MUST COMPLY WITH | | 250.140, 4 WIRE. | | | | 8} THE LAUNDRY CIRCUIT MUST BE | | CALCULATED @ 1500VA PER 220.16(B). | | | | ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPON- | | SIBLE FOR THE DESIGN. SECTION 104.2.1 | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|