2004-10-06 00:00:00********* UNSAT 2ND REVIEW **********
  
 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED,DATED AND SEAL BY THE ENGINEER
 OF RECORD . FS 471.025
 PLEASE SEE PLANS ARE PHOTOCOPIES OF WHAT
 APPEARS TO BE SIGNED AND SEALED PLANS???
  
 2)NOTE: PLEASE SEE CONTINUOUS LOADS ARE
 TO BE SHOWN AT 125%.
 215.3,230.42 ETC
  
 3)NOTE: PLEASE CLARIFY WHERE POLE INFOR-
 -MATION AND WIND LOADS ARE NOTED ON ELEC
 -TRICAL PLANS?
 IS ABOVE INFORMATION ON OTHER SHEETS.
 COULD ONLY LOCATE NOTE ON SP-1??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  