2004-08-04 00:00:00FAILED:
 1. CIVIL SITE PLANS MUST BE REVIEWED AND
 AND APPROVED FOR ALL THE CONNECTION TO
 THE SREVICES, NO METER, DDCV FOR FIRE
 LINE OR BACKFLOWS FOR DOMESTIC ARE SHOWN
 SHEET 6 OF 10, NOTE THAT A SEPARATE
 BACKFLOWS FOR EACH BUILDING PER PLUMBING
 CODE IS REQUIRED.
 2. PLEASE PROVIDE STORM WATER CALC. FOR
 OUR REVIEW AND APPROVAL, INCLUDE
 PERVIOUS AND IMPERVIOUS AREA, BUILDING
 AREA FOR THE ENITRE SITE.
 3. WORK IN PUBLIC R.O.W REQUIRES A
 SEPARATE PERMIT FROM THE PUBLIC
 UTILITIES AND ENGINEERING, WINDEL PALMER
 494-1086 AND FROM PB COUNTY WILL BE
 REQUIRED.
 4. A SEPARATE PERMIT FOR SITE ELECTRICAL
 WORK IS REQUIRED.
 5. LANDSCAPING PLAN MUST BE REVIEWED AND
 APPROVED BY PLANNING AND ZONING, IT
 SHOULD BE PART OF BUILDING PERMIT
 APPLICATION SBMITTALS.
 IF ANY QUESTION PLEASE CONTACT 805-6723