Plan Review Notes
Plan Review Notes For Permit 04071137
Permit Number 04071137
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-02 00:00:00********** UNSAT ********************
  
 1)NOTE:PLEASE SEE 2002 NEC FOR REQUIRED
 ARC FAULT PROTECTION. SD'S, RECEPTS,
 LTS FANS ETC. NOT ONLY RECEPTS.
  
 2 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 SOME MISSING.
  
 4)NOTE: PLEASE CORRELATE A/C KW RATINGS,
  
 LOAD CALCS INDICATE 10KW EACH , YET
 PANEL SCHEDULE INDICATE S5KW.
  
 5)NOTE: PLEASE SEE250.50, GRND ELECT-
 -RODE CONDCUTOR TO COLD WATER (IF METAL)
 ND FOOTER STEEL.
  
 6)NOTE; SD IN HALLWAY TO BE MOVED INTO
 MASTER BEDRM. NFPA-72 8-1.4.1.6.2
  
 7)NOTE: PLEASE SEE 110.26 FOR DISC
 CLEARENCES AT COND UNITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]