Plan Review Notes For Permit 04071137 |
Permit Number |
04071137 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-02 00:00:00 | ********** UNSAT ******************** | | | | 1)NOTE:PLEASE SEE 2002 NEC FOR REQUIRED | | ARC FAULT PROTECTION. SD'S, RECEPTS, | | LTS FANS ETC. NOT ONLY RECEPTS. | | | | 2 NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | 3) NOTE: PLEASE SHOW OUTLET SPACING PER | | 210.52. 2',6`,12` RULE. | | SOME MISSING. | | | | 4)NOTE: PLEASE CORRELATE A/C KW RATINGS, | | | | LOAD CALCS INDICATE 10KW EACH , YET | | PANEL SCHEDULE INDICATE S5KW. | | | | 5)NOTE: PLEASE SEE250.50, GRND ELECT- | | -RODE CONDCUTOR TO COLD WATER (IF METAL) | | ND FOOTER STEEL. | | | | 6)NOTE; SD IN HALLWAY TO BE MOVED INTO | | MASTER BEDRM. NFPA-72 8-1.4.1.6.2 | | | | 7)NOTE: PLEASE SEE 110.26 FOR DISC | | CLEARENCES AT COND UNITS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|