Plan Review Notes
Plan Review Notes For Permit 04071137
Permit Number 04071137
Review Stop B
Sequence Number 1
Notes
Date Text
2004-08-09 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SPECIFY THE SIZE AND REINFORCING FOR
 THE INTERIOR FOOTINGS AT THE FOYER AREA
 ON SHEET A-1.0.
  
 3) PLEASE CLARIFY THE WOOD POST THAT IS
 SHOWN AT THE CORNER OF THE DEN WALL ON
 SHEETS A-1.0 AND A-2.0.
  
 4) THERE IS NO FOOTER INFORMATION GIVEN
 ON A-1.0 FOR THE SHOWER RECESS AT BATH 2
  
 5) SPECIFY THAT THE WIRE MESH IN THE
 SLAB WILL BE SUPPORTED AT 3 FEET O.C.
 SEE FBC 1909.3.
  
 6) THE WRONG WINDOWS ARE SPECIFIED AS
 EGRESS WINDOWS IN THE SCHEDULE ON A-2.0.
  
 7) THIS JURISDICTION IS LOCATED IN A
 WIND-BORNE DEBRIS REGION. EXTERIOR
 GLAZED OPENINGS ARE REQUIRED TO BE
 PROTECTED OR HAVE IMPACT RESISTANT
 GLAZING PER FBC 1606.1.4. SPECIFY HOW
 THIS WILL BE ACCOMPLISHED.
  
 8) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 9)FBC 1005.4.5 (GLITCH AMENDMENTS
 JULY 1, 2003) REQUIRES AT LEAST ONE
 MEANS OF ESCAPE FROM A DWELLING WHEN
 SHUTTERED FOR IMPACT PROTECTION. THE
 MEANS OF ESCAPE SHALL BE WITHIN THE
 FIRST FLOOR OF THE DWELLING AND CAN NOT
 BE LOCATED IN A GARAGE. OCCUPANTS IN ANY
 PART OF THE DWELLING SHALL HAVE ACCESS
 TO IT WITHOUT HAVING TO PASS THROUGH A
 LOCKABLE DOOR NOT UNDER THEIR CONTROL.
 INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
 10) SPECIFY THE DESIGN WIND PRESSURES
 FOR THE GLASS BLOCK OPENINGS ON A-4.0.
  
 11) CLARIFY THE NUMBERING OF THE NET
 UPLIFT NOTES ON A-5.0.
  
 12)SPECIFY THE WELD TYPE FOR THE 3 GUAGE
 STEEL PLATE HANGER IN DETAIL 2 ON A-5.0.
  
 13) CLARIFY THE REQUIRED NAILING FOR THE
 THE (2) H2.5A CONNECTORS IN THE SCHEDULE
 ON A-5.0. THE 2004 SIMPSON CATALOG
 REQUIRES (5) 8D NAILS IN THE TRUSS AND
 (5) IN THE PLATE FOR EACH CONNECTOR.
  
 14) CORRECT THE TYPO IN THE SCHEDULE FOR
 THE HETAI-20 AT MARK (D).
  
 15) REVISE THE WIRE LATH NOTE ON D-1.
 ASTM C 1063 REQUIRES 3/8" RIB LATH TO BE
 FASTENED AT EVERY RIB (4"O.C.) AND THE
 NAILS OR STAPLES ARE TO PROVIDE AT LEAST
 1-3/4" PENETRATION INTO HORIZONTAL WOOD
 FRAMING MEMBERS. SEE FBC 2504.2.2
  
 16) CONFLICTING GARAGE DOOR BUCK SPECS.
 ARE GIVEN ON D-1.
  
 17) SPECIFY THE FASTENERS FOR THE LUS 26
 HANGER IN DETAIL 4 AND THE HU 212-2
 HANGER IN DETAIL 5 ON SHEET D-1.
  
 18) THE GLASS BLOCK DETAIL ON D-2
 REFERENCES THE WRONG CODE & SECTION.
  
 19) PROVIDE A DETAIL FOR CONSTRUCTING
 THE ARCHED WINDOW OPENINGS IN THE BLOCK
 WALLS.
  
 20) SUBMIT PRODUCT FLORIDA APPROVAL FOR
 THE GLASS BLOCK.
  
 21) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING FOR THE ONE HOUR FIRE
 RATED GLASS BLOCK ON THE ZERO LOT LINE.
  
 22) SUBMIT THE FL NUMBERS FOR THE TWO
 GARAGE DOORS.
  
 23) THE PRODUCT APPROVALS FOR THE FRENCH
 DOORS ARE NOT RATED FOR IMPACT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714