2004-08-09 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SPECIFY THE SIZE AND REINFORCING FOR |
| THE INTERIOR FOOTINGS AT THE FOYER AREA |
| ON SHEET A-1.0. |
| |
| 3) PLEASE CLARIFY THE WOOD POST THAT IS |
| SHOWN AT THE CORNER OF THE DEN WALL ON |
| SHEETS A-1.0 AND A-2.0. |
| |
| 4) THERE IS NO FOOTER INFORMATION GIVEN |
| ON A-1.0 FOR THE SHOWER RECESS AT BATH 2 |
| |
| 5) SPECIFY THAT THE WIRE MESH IN THE |
| SLAB WILL BE SUPPORTED AT 3 FEET O.C. |
| SEE FBC 1909.3. |
| |
| 6) THE WRONG WINDOWS ARE SPECIFIED AS |
| EGRESS WINDOWS IN THE SCHEDULE ON A-2.0. |
| |
| 7) THIS JURISDICTION IS LOCATED IN A |
| WIND-BORNE DEBRIS REGION. EXTERIOR |
| GLAZED OPENINGS ARE REQUIRED TO BE |
| PROTECTED OR HAVE IMPACT RESISTANT |
| GLAZING PER FBC 1606.1.4. SPECIFY HOW |
| THIS WILL BE ACCOMPLISHED. |
| |
| 8) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 9)FBC 1005.4.5 (GLITCH AMENDMENTS |
| JULY 1, 2003) REQUIRES AT LEAST ONE |
| MEANS OF ESCAPE FROM A DWELLING WHEN |
| SHUTTERED FOR IMPACT PROTECTION. THE |
| MEANS OF ESCAPE SHALL BE WITHIN THE |
| FIRST FLOOR OF THE DWELLING AND CAN NOT |
| BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| PART OF THE DWELLING SHALL HAVE ACCESS |
| TO IT WITHOUT HAVING TO PASS THROUGH A |
| LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| INDICATE HOW COMPLIANCE WILL BE |
| ACHIEVED. |
| |
| 10) SPECIFY THE DESIGN WIND PRESSURES |
| FOR THE GLASS BLOCK OPENINGS ON A-4.0. |
| |
| 11) CLARIFY THE NUMBERING OF THE NET |
| UPLIFT NOTES ON A-5.0. |
| |
| 12)SPECIFY THE WELD TYPE FOR THE 3 GUAGE |
| STEEL PLATE HANGER IN DETAIL 2 ON A-5.0. |
| |
| 13) CLARIFY THE REQUIRED NAILING FOR THE |
| THE (2) H2.5A CONNECTORS IN THE SCHEDULE |
| ON A-5.0. THE 2004 SIMPSON CATALOG |
| REQUIRES (5) 8D NAILS IN THE TRUSS AND |
| (5) IN THE PLATE FOR EACH CONNECTOR. |
| |
| 14) CORRECT THE TYPO IN THE SCHEDULE FOR |
| THE HETAI-20 AT MARK (D). |
| |
| 15) REVISE THE WIRE LATH NOTE ON D-1. |
| ASTM C 1063 REQUIRES 3/8" RIB LATH TO BE |
| FASTENED AT EVERY RIB (4"O.C.) AND THE |
| NAILS OR STAPLES ARE TO PROVIDE AT LEAST |
| 1-3/4" PENETRATION INTO HORIZONTAL WOOD |
| FRAMING MEMBERS. SEE FBC 2504.2.2 |
| |
| 16) CONFLICTING GARAGE DOOR BUCK SPECS. |
| ARE GIVEN ON D-1. |
| |
| 17) SPECIFY THE FASTENERS FOR THE LUS 26 |
| HANGER IN DETAIL 4 AND THE HU 212-2 |
| HANGER IN DETAIL 5 ON SHEET D-1. |
| |
| 18) THE GLASS BLOCK DETAIL ON D-2 |
| REFERENCES THE WRONG CODE & SECTION. |
| |
| 19) PROVIDE A DETAIL FOR CONSTRUCTING |
| THE ARCHED WINDOW OPENINGS IN THE BLOCK |
| WALLS. |
| |
| 20) SUBMIT PRODUCT FLORIDA APPROVAL FOR |
| THE GLASS BLOCK. |
| |
| 21) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| AND UL LISTING FOR THE ONE HOUR FIRE |
| RATED GLASS BLOCK ON THE ZERO LOT LINE. |
| |
| 22) SUBMIT THE FL NUMBERS FOR THE TWO |
| GARAGE DOORS. |
| |
| 23) THE PRODUCT APPROVALS FOR THE FRENCH |
| DOORS ARE NOT RATED FOR IMPACT. |
| |