Plan Review Notes
Plan Review Notes For Permit 04071132
Permit Number 04071132
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-02 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SEE SERVICE IS BEING
 SHOWN AS 225A'S YET SEC'S ARE ONLY
 RATED FOR 200A'S.
  
 3 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC 210.12B
 NOT ONLY RECEPTS. SD'S SHOWN ON BATH LT
 CIRCUIT?
  
 4)NOTE: PLEASE SEE MISSING FOOTER STEEL
 AND CWP AS PART OF GROUNDING ELECTRODE
 SYSTEM. 250.50
  
 5)NOTE: PLEASE SEE FOYER WILL REQUIRE
 A LT FIX OF SOME SORT FOR MEANS OF
 EGRESS. 210.70/LS101.5-8
  
 6)NOTE: PLEASE SEE SD IN MASTER HALL TO
 BE MOVED INTO BEDRM.
 NFPA-72 8-1.4.1.6.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717