2005-08-03 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEERISER DIAGRAM HAS
 BEEN REVISED TO INDICATE NO "POOL
 PANEL", HOWEVER MAIN PANEL STILL SHOWS
 POOL PANEL?
 PLEASE CORRELATE.215.5
  
  
 2)NOTE: PLEASE SEE REFERENCE TO 1999 NEC
 FOR ARC FAULT PROTECTION.
 210.12
  
  
 3)NOTE: PLEASE SEE PLANS DO NOT INDICATE
 THE NEW "MAIN DISCONNECT" AS SHOWN ON
 RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  