Plan Review Notes
Plan Review Notes For Permit 04071122
Permit Number 04071122
Review Stop E
Sequence Number 1
Notes
Date Text
2004-08-02 00:00:00*********** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 2002 NEC, ARC FAULT PROTECTIONS IS ON
 BRANCH CIRCUIT, NOT AT/IN DEVICES IN
 BEDRMS.
 210.12B
  
 3)NOTE: PLEASE SEE FOOTER STEEL AND
 COLD WATER PIPE TO SHOWN AS PART OF
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 4)NOTE: PLEASE SEE 110.26 FOR CLEARENCE
 OF DISC FOR COND UNIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]