Plan Review Notes For Permit 04071122 |
Permit Number |
04071122 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-02 00:00:00 | *********** UNSAT *************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | RATED FOR THE AVAILABLE FAULT CURRENT. | | PER 110.9/215.5 | | | | 2 )NOTE: PLEASE LIST THE REQ'D ARC | | FAULT PROTECTED CURCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | 2002 NEC, ARC FAULT PROTECTIONS IS ON | | BRANCH CIRCUIT, NOT AT/IN DEVICES IN | | BEDRMS. | | 210.12B | | | | 3)NOTE: PLEASE SEE FOOTER STEEL AND | | COLD WATER PIPE TO SHOWN AS PART OF | | GROUNDING ELECTRODE SYSTEM. 250.50 | | | | 4)NOTE: PLEASE SEE 110.26 FOR CLEARENCE | | OF DISC FOR COND UNIT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|