2004-10-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEW: NUMBER FOR COMMENT
 WILL REMAIN THE SAME AS FIRST REVIEW TO
 AVOID CONFUSION.
  
 3) SHT A5 SUBMIT CALCULATIONS FOR PRIM-
 ARY AND SECONDARY ROOF DRAINS PER SECT-
 IONS 1106 & 1107. SHOW SQUARE FOOTAGE OF
 THE ROOF AND 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS BEING ADDED TO
 SF OF ROOF AREA. (THIS INCLUDES THE WALL
 OF THE ADJACENT EXISTING BUILDING IF THE
 BLDGS ARE ATTACHED).
 6) SUBMIT A WATER RISER DIAGRAM REQUIRED
 BY SECTION 104.3.1.1. (NOTE: AIR CHAMB-
 ERS ARE NOT APPROVED. WATER HAMMER ARR-
 ESTORS REQUIRED BY SECTION 604.9 SHALL
 BE LOCATED IN AN EFFECTIVE RANGE PER
 PDI-WH 201 AND MANUF. INSTALLATION RE-
 QUIREMENTS.
 *********NEW COMMENT
 1B SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS553.80(2)(B).
  
 REVIEW BY KEN STEVENS