Plan Review Notes
Plan Review Notes For Permit 04071120
Permit Number 04071120
Review Stop E
Sequence Number 2
Notes
Date Text
2004-09-23 00:00:00**** UNSAT ****
  
 PLEASE SEE PLANS ARE COMING BACK FOR
 OTHER COMMENTS, PLEASE ADDRESS THE
 FOLLOWING AT THIS TIME.
  
 1)NOTE: PLEASE SEE NOTE FROM FIRST RE-
 -VIEW: PLEASE SEE 250.6,250.24, AN
 EQUIPMENT GROUNDING CONDUCTOR IS STILL
 SHOWN FROM METER TO FIRST MEANS OF DISC-
 -ONNECT. PLEASE SEE ABOVE CODE, ONLY
 AFTER FIRST MEANS OF DISC.
  
 2)NOTE: PLEASE SEE 250.50, FOOTER STEEL
 IS REQUIRED ALONG WITH OTHER CONNECTION
 POINTS WHERE AVAILABLE.
 PLEASE INDICATE THESE POINTS ON GROUND-
 -ING ELECTRODE DETAIL FOR POINTS OF
 ATTACHMENT FOR THIS BLDG.
 215.5
  
 3)NOTE: PLEASE SEE FLOOR PLAN INDICATES
 TWO "ELECTRICAL PANELS", ONLY ONE SHOWN
 ON RISER? (MISPRINT)
  
 4)NOTE: PLEASE SEE "SHOW WINDOW" RECEPTS
 ARE REQUIRED FOR DISPLAY/ADVERTISEMENT.
 PLEASE SHOW. 210.62
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]