2004-10-06 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04071120 |
| ADD: 1308 CLARE AV |
| CONT: BATTEN CONSTRUCTION |
| TEL: (561)662-0309 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH LOCAL AMENDMENTS |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) LEGAL ISSUES: |
| A) PROVIDE DEAD SHOWING OWNERSHIP |
| B) PROVIDE DOCUMENTS FOR LOT SPLIT, SEE |
| PLANNING. |
| C) PROVIDE UNITY OF TITLE FOR LOTS |
| 1,2&3. |
| |
| 3) FROM PREVIOUS REVIEW, COMMENT# 6 DELT |
| WITH THE RATING OF THE EXTERIOR WALL |
| 0-3' FROM THE PROPERTY LINE. FOR TYPE IV |
| CONSTRUCTION THIS IS A 2 HR RATED BLOCK, |
| SHEET A4 INDICATES THE USE OF UL BLOCK, |
| PROVIDE THE EQUIVANT THICKNESS FOR BLOCK |
| SUPPLIED BY UL. IF YOUR BLOCK IS TO BE |
| SUPPLIED BY RINKER, THEN THE EQUIVALENT |
| THICKNESS (TABLE 709.3.1) OF THE BLOCK |
| WOULD BE SUPPLIED BY RINKER. |
| |
| 4) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) EXTERIOR LOUVERS. |
| |
| 5)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| IF THE PRODUCT APPROVALS SUBMITTED |
| DO NOT HAVE "STATE APPROVAL" THEN LOCAL |
| PRODUCT APPROVAL WILL BE REQUIRED. |
| A) PROVIDE THE INDEPENDENT THIRD PARTY |
| QUALITY ASSURANCE PRORGAM IF NOT DADE |
| COUNTY NOA. |
| B) FOR THE CERTIFIIED TESTING REPORT, |
| THIS MUST BE A SEALED REPORT WITH |
| THE 3RD PARTY QUALITY ASSURANCE |
| ENTITY AND LOCAL PRODUCT APPROVAL |
| COVER SHEET FILLED OUT. |
| |
| 6)FBC 13-103.1.2 BEFORE A BUILDING |
| PERMIT CAN BE ISSUED, THE SUBMITTED |
| ENERGY CODE COMPLIANCE FORMS SHALL BE |
| SIGNED BY THE BUILDING OWNER, THE |
| OWNER'S ARCHETECT OR OTHER AUTHORIZED |
| AGENT LEGALLY DESIGNATED BY THE OWNER. |
| |
| 7)PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 2001 FLORIDA ENERGY |
| EFFICIENTCY CODE FOR BUILDING CONSTRUC- |
| TION. |
| |
| 8) THE WAREHOUSE REQUIRES 2 MEAN OF |
| EGRESS, THE EGRESS THROUGH THE DOOR# 4 |
| INTO THE RETAIL AREA CAN ONLY HAVE AN |
| EXIT LIGHT ON THE WAREHOUSE SIDE. THE |
| EXIT LIGHT ON THE RETAIL SIDE TO BE RE- |
| MOVED. YOU CAN NOT TAKE A PERSON THROUGH |
| A MORE DANGEROUS OCCUPANCY. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |