2004-10-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071120
 ADD: 1308 CLARE AV
 CONT: BATTEN CONSTRUCTION
 TEL: (561)662-0309
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH LOCAL AMENDMENTS
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) LEGAL ISSUES:
 A) PROVIDE DEAD SHOWING OWNERSHIP
 B) PROVIDE DOCUMENTS FOR LOT SPLIT, SEE
 PLANNING.
 C) PROVIDE UNITY OF TITLE FOR LOTS
 1,2&3.
  
 3) FROM PREVIOUS REVIEW, COMMENT# 6 DELT
 WITH THE RATING OF THE EXTERIOR WALL
 0-3' FROM THE PROPERTY LINE. FOR TYPE IV
 CONSTRUCTION THIS IS A 2 HR RATED BLOCK,
 SHEET A4 INDICATES THE USE OF UL BLOCK,
 PROVIDE THE EQUIVANT THICKNESS FOR BLOCK
 SUPPLIED BY UL. IF YOUR BLOCK IS TO BE
 SUPPLIED BY RINKER, THEN THE EQUIVALENT
 THICKNESS (TABLE 709.3.1) OF THE BLOCK
 WOULD BE SUPPLIED BY RINKER.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR LOUVERS.
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 IF THE PRODUCT APPROVALS SUBMITTED
 DO NOT HAVE "STATE APPROVAL" THEN LOCAL
 PRODUCT APPROVAL WILL BE REQUIRED.
 A) PROVIDE THE INDEPENDENT THIRD PARTY
 QUALITY ASSURANCE PRORGAM IF NOT DADE
 COUNTY NOA.
 B) FOR THE CERTIFIIED TESTING REPORT,
 THIS MUST BE A SEALED REPORT WITH
 THE 3RD PARTY QUALITY ASSURANCE
 ENTITY AND LOCAL PRODUCT APPROVAL
 COVER SHEET FILLED OUT.
  
 6)FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 7)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 8) THE WAREHOUSE REQUIRES 2 MEAN OF
 EGRESS, THE EGRESS THROUGH THE DOOR# 4
 INTO THE RETAIL AREA CAN ONLY HAVE AN
 EXIT LIGHT ON THE WAREHOUSE SIDE. THE
 EXIT LIGHT ON THE RETAIL SIDE TO BE RE-
 MOVED. YOU CAN NOT TAKE A PERSON THROUGH
 A MORE DANGEROUS OCCUPANCY.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026