2004-08-10 00:00:00 | ************* UNSAT **************** |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH SUBMITTED. |
| PLEASE SEE 700.12E FOR CIRCUITING OF EM/ |
| EXT LTS. |
| |
| 2)NOTE: PLEASE INCLUDE/IDENTIFY SEC'S |
| IN RISER TO METER. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| SYSTEM TO METER CAN, PLEASE SEE 250.66 |
| WHICH REQUIRES A MIN OF #4. |
| NOTES MENTIONS #6 |
| GEC REQUIRED TO CWP AND FOOTER STEEL AS |
| A MIN. 250.50 |
| PLEASE ALSO SEE NOTE #2 MENTIONS AN |
| EQUIPMENT GROUNDING CONDUCTOR FROM METER |
| CAN TO THE FIRST MEANS OF DISCONNECT.? |
| PLEASE SEE 250.24,250.6. EQUIPMENT GRNDS |
| ARE ONLY INSTALLED AFTER THE FIRST MEANS |
| OF DISCONNECT. |
| |
| 4)NOTE: |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 ETC. |
| IT WAS NOTED THAT A/C LOAD WAS INDICATED |
| AT 125%. |
| |
| PLEASE SEE ANY COMMENTS FROM OTHER |
| REVIEWERS AS THEY MAY HAVE AN AFFECT ON |
| THE ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO COMPLETED |
| SETS FOR REVIEW AND STAMPING. |
| |
| ***PLEASE NOTE: THIS PLAN IS ONLY IN FOR |
| "PLAN REVIEW" ONLY AND NOT FOR PERMIT AT |
| THIS TIME. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |