2004-08-10 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
  
 2)NOTE: PLEASE INCLUDE/IDENTIFY SEC'S
 IN RISER TO METER.
 215.5
  
 3)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM TO METER CAN, PLEASE SEE 250.66
 WHICH REQUIRES A MIN OF #4.
 NOTES MENTIONS #6
 GEC REQUIRED TO CWP AND FOOTER STEEL AS
 A MIN. 250.50
 PLEASE ALSO SEE NOTE #2 MENTIONS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM METER
 CAN TO THE FIRST MEANS OF DISCONNECT.?
 PLEASE SEE 250.24,250.6. EQUIPMENT GRNDS
 ARE ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 4)NOTE:
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42 ETC.
 IT WAS NOTED THAT A/C LOAD WAS INDICATED
 AT 125%.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWERS AS THEY MAY HAVE AN AFFECT ON
 THE ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO COMPLETED
 SETS FOR REVIEW AND STAMPING.
  
 ***PLEASE NOTE: THIS PLAN IS ONLY IN FOR
 "PLAN REVIEW" ONLY AND NOT FOR PERMIT AT
 THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  