2004-08-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04071120
 ADD: 1308 CLARE AV
 CONT: "PLAN REIEW"
 CONTACT: WILSON-ROWAN
 TEL: (561)833-5647
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.SUBMIT A COPY OF THE 'UNITY
 OF TITLE' DOCUMENT SO THAT FBC TABLE 600
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
 3)61G15-23.002 P. E.- CERTIFICATE OF
 AUTHORIZATION.IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 4) PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". FLOOD ZONE A9=13'-6".
  
 5) SITE IS LOCATED IN A FIRE DISTRICT:
 A) NO TYPE VI CONSTRUCTION
 B) FBC* F102.2.4ROOF COVERINGS, ON
 BUILDINGS LOCATED IN THE FIRE DISTRICT,
 SHALL CONFORM TO THE REQUIREMENTS OF
 CLASS A OR B ROOF COVERINGS, AS DEFINED
 IN FBC 1505.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
 C) FBC* F102.2.7ARCHITECTURAL TRIM,
 ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 6) PLANS DO NOT PROVIDE WHAT THE MINIMUM
 BUILDING TYPE IS? NOTE, TYPE V CONSTRUC-
 TION 0-3' FROM PROPERTY LINE REQUIRES A
 3 HR RATINGFOR BEARING & NON-BEARING
 WALLS. SHEET A4 INDICATES THE BACK WALL
 OF THE STRUCTURE BEING A 2 HR WALL. A
 3HR WALL IS REQUIRED FOR TYPE V CONSTRUC
 TION. PROVIDE THE EQUIVALENT THICKNESS
 (TABLE 709.3.1.) REPORT TO BE SUPPLIED
 BY THE BLOCK MANUFACTURER.
  
 7) SHEET A5 WIND LOAD PRESSURES CHART,
 IF THESE PRESSURES ARE FOR THE COMPOEN-
 ENTS AND CLADDING SEE TABLE 1606.2B &
 1606.2E. PRESSURES ARE LOW.
  
 8) SAME SHEET INDICATES THE USE OF ROOF
 SCUPPERS BUT NOT OVERFLOWS. SEE SECTION:
 1503.4.2 OVERFLOW DRAINS SHALL BE
 THE SAME SIZE AS ROOF DRAINS, INSTALLED
 WITH THE INLET FLOW LINE LOCATED 2"
 ABOVE THE LOWEST POINT OF THE ROOF LINE.
 OVERFLOW SCUPPERS SHALL BE A MINIMUM OF
 4"IN HEIGTH AND SHALL BE PLACED IN WALLS
 OR PARARETS WITH THE INLET FLOW LINE
 NOT LESS THAN 2" ABOVE THE ROOF SURFACE.
  
 9) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 10)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
  
 11)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR LOUVERS
 B) ROOFING ASSEMBLIES, INSULATION +
 ROOFING MATERIALS
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)PROVIDE ENERGY CALCULATIONS AND
 EQUIPMENT SIZING CALCULATIONS (MANUAL J)
 AS REQUIRED BY THE 2001 FLORIDA ENERGY
 EFFICIENTCY CODE FOR BUILDING CONSTRUC-
 TION.
  
 14) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 15) WAREHOUSE REQUIRES 2 EXITS DOESN'T
 MEET THE REQUIREMENTS OF 1027.1.1 FOR
 SINGLE EXIT. THE 2ND EXIT CAN BE THE
 DOORWAY BETWEEN THE WAREHOUSE AND
 OFFICE, IT MEETS THE REUIREMENTS OF OVER
 1/2 OF THE DIAGONAL. THE EXIT SIGN SHOWN
 ON THE BUSINESS SIDE SHOULD BE ON THE
 WAREHOUSE SIDE. SEE A6.
  
 16)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026