Plan Review Notes For Permit 04071021 |
Permit Number |
04071021 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-26 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SUBMIT CONDUIT & WIRE SIZE FOR ALL | | NEW WIRING BEING INSTALLED OR EXISTING | | WIRING BEING REUSED. | | | | 2} INDICATE THE NAMEPLATE RATING OF THE | | UNIT(S) BEING INSTALLED.IF ADDED UNITS | | OR LARGER REPLACEMENT UNITS, PROVIDE | | LOAD CALCS. | | | | 3} INDICATE CIRCUIT NUMBERS BEING USED. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|