2004-08-05 00:00:00DENIED:
 PLEASE PROVIDE ADDITIONAL INFORMATION
 ON A/C SYSTEM #1 & 3.PROVIDE
 MANUFACTURER CONFIRMATION THAT AHU 1 &
 3 DOES NOT HAVE THE CAPACITY TO OUTPUT
 GREATER THAN 2,000 CFM.
  
 PLAN SHEET M1, DUCT & GRILLE SIZE
 MISSING ON 1 BRANCH LINE FROM SYSTEM
 2 AND ONE BRANCH LINE FROM SYSTEM 1.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  