Plan Review Notes For Permit 04071011 |
Permit Number |
04071011 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-05 00:00:00 | DENIED: | | PLEASE PROVIDE ADDITIONAL INFORMATION | | ON A/C SYSTEM #1 & 3.PROVIDE | | MANUFACTURER CONFIRMATION THAT AHU 1 & | | 3 DOES NOT HAVE THE CAPACITY TO OUTPUT | | GREATER THAN 2,000 CFM. | | | | PLAN SHEET M1, DUCT & GRILLE SIZE | | MISSING ON 1 BRANCH LINE FROM SYSTEM | | 2 AND ONE BRANCH LINE FROM SYSTEM 1. | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|