Plan Review Notes
Plan Review Notes For Permit 04071011
Permit Number 04071011
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-27 00:00:00********** NOTES REDLINED ************
  
 1)NOTE: PLEASE SEE 210.63 FOR MISSING
 ROOFTOP GFI RECEPT.
  
 2)NOTE: PLEASE CORRELATE ALL OCP, AWG
 AND LOADS FOR AHU'S/ A/C SYSTEMS.
 PLEASE SEE 424.3B FOR SIZING OF OCP.
  
 THE ABOVE HAS BEEN REDLINED AND THERE IS
 NO NEED FOR CORRECTION AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 ELETCRICAL PLAN REVIEW