Plan Review Notes
Plan Review Notes For Permit 04070961
Permit Number 04070961
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} HAND DRAWN REVISIONS MUST BE
 INITIALED BY THE DESIGNER OF RECORD.
 PASTED ON NOTES AND SCHEDULES ARE NOT
 ACCEPTABLE.
  
 2} THE SEAL OF THE DESIGNER MUST
 CONTAINTHE DATE SEALED PER 61G1-16.003
 FAC.
  
 3} THE TITLE BLOCK MUST CONTAIN ALL
 INFORMATION REQUIRED BY 61G1-16.004 FAC.
 INCLUDING FIRM #, TELEPHONE NUMBER AND
 ADDRESS. SEE FS 481 AND RELEVANT
 ADMINISTRATIVE CODES.
  
 4} PLEASE RECALCULATE THE LOAD AND
 CHANGE PANEL SCHEDULE TO REFLECT THE
 ADDED RECESSED LUMINAIRES PER
 220.3(B)(4) NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026