Plan Review Notes
Plan Review Notes For Permit 04070958
Permit Number 04070958
Review Stop E
Sequence Number 4
Notes
Date Text
2006-09-22 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 250.52(A)(3) CONCRETE-ENCASED
 ELECTRODE.
 AN ELECTRODE ENCASED BY AT LEAST 50 MM
 (2 IN.) OF CONCRETE, LOCATED WITHIN AND
 NEAR THE BOTTOM OF A CONCRETE FOUNDATION
 OR FOOTING THAT IS IN DIRECT CONTACT
 WITH THE EARTH, ETC.IF THE SERVICE IS
 NEW THIS REQUIREMENT SHOULD HAVE BEEN
 ADDRESED WHEN FOOTER STEEL WAS
 INSTALLED. ISSUES LIKE THIS IS WHY WE
 REQUIRE THE PROPOSED WORK BE COMPLETE
 AND CORRECT ON THE PLANS SUBMITTED FOR
 REVIEW.
  
 2} THE EQUIPMENT GROUNDING CONDUCTOR
 MUST COMPLY WITH 250.66. THE NOTE ON THE
 COMMENT SHEET STATINDG THAT THE #4 IS
 "OVERSIZED" IS INCORRECT. THE LARGEST
 SERVICE ENTRANCE CONDUCTOR AS STATED IN
 250.66 IS PARALLEL 2/0. SEE EXHIBIT
 250.28 IN THE HANDBOOK FOR
 CLARIFICATION. THE DESIGNER INDICATES A
 400 AMP SERVICE IS BEING SUPPLIED. 400
 MCM WOULD BE A 1/0 GEC. IF THE EXAMPLE
 IN THE HANDBOOK IS USED, THE GEC WOULD
 BE #2CU,(133100CMX2, ROUNDED UP) THEN
 TECHNICALLY THE SERVICE IS ONLY RATED
 FOR 350 AMPS.
  
 3} THE CONDUCTOR SIZES WERE REMOVED FROM
 THE SCHEDULE, PLEASE PUT THEM BACK ON
 SOTHAT OCP AND CONDUCTOR SIZE CAN BE
 REVIEWED FOR COMPLIANCE PER 310.16.
  
 4} CIRCUIT #B5 IS MARKED AS A SMALL
 APPLIANCE CIRCUIT IN THE SCHEDULE, BUT
 IS THE BATH CIRCUIT ON TEH PLAN.
  
 5} AHU #1 IS NOT LISTED ON THE SCHEDULE.
  
 6} A/C COMPRESSER #1 IS NOT LISTED AND
 HAS THE WRONG CIRCUIT NUMBERS AT THE
 UNIT ON THE PLAN.
  
 7} PER 210.12 CIRCUIT G5 (SMOKE
 DETECTORS) MUST BE ON A AFCI. THEY
 CANNOT BE ON THE BATHROOM CIRCUIT, SEE
 210.11(C)(3).
  
 8} THE INITIALS ON THE ARCHITECTS SEAL
 IS NOT THE SAME AS THE "SIGNATURE" ON
 THE SEAL DATED 8/13/04. THE ARCHITECT
 MUST SIGN HIS SEAL PER 61G1-16.003
 FLORIDA ADMINISTRATIVE CODE. ONE SET OF
 PLANS IS BEING RETAINED BY THIS OFFICE
 WITH THIS APPARANTLY UNAUTHORIZED "
 SIGNATURE".
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  