2006-09-22 00:00:00 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} 250.52(A)(3) CONCRETE-ENCASED |
| ELECTRODE. |
| AN ELECTRODE ENCASED BY AT LEAST 50 MM |
| (2 IN.) OF CONCRETE, LOCATED WITHIN AND |
| NEAR THE BOTTOM OF A CONCRETE FOUNDATION |
| OR FOOTING THAT IS IN DIRECT CONTACT |
| WITH THE EARTH, ETC.IF THE SERVICE IS |
| NEW THIS REQUIREMENT SHOULD HAVE BEEN |
| ADDRESED WHEN FOOTER STEEL WAS |
| INSTALLED. ISSUES LIKE THIS IS WHY WE |
| REQUIRE THE PROPOSED WORK BE COMPLETE |
| AND CORRECT ON THE PLANS SUBMITTED FOR |
| REVIEW. |
| |
| 2} THE EQUIPMENT GROUNDING CONDUCTOR |
| MUST COMPLY WITH 250.66. THE NOTE ON THE |
| COMMENT SHEET STATINDG THAT THE #4 IS |
| "OVERSIZED" IS INCORRECT. THE LARGEST |
| SERVICE ENTRANCE CONDUCTOR AS STATED IN |
| 250.66 IS PARALLEL 2/0. SEE EXHIBIT |
| 250.28 IN THE HANDBOOK FOR |
| CLARIFICATION. THE DESIGNER INDICATES A |
| 400 AMP SERVICE IS BEING SUPPLIED. 400 |
| MCM WOULD BE A 1/0 GEC. IF THE EXAMPLE |
| IN THE HANDBOOK IS USED, THE GEC WOULD |
| BE #2CU,(133100CMX2, ROUNDED UP) THEN |
| TECHNICALLY THE SERVICE IS ONLY RATED |
| FOR 350 AMPS. |
| |
| 3} THE CONDUCTOR SIZES WERE REMOVED FROM |
| THE SCHEDULE, PLEASE PUT THEM BACK ON |
| SOTHAT OCP AND CONDUCTOR SIZE CAN BE |
| REVIEWED FOR COMPLIANCE PER 310.16. |
| |
| 4} CIRCUIT #B5 IS MARKED AS A SMALL |
| APPLIANCE CIRCUIT IN THE SCHEDULE, BUT |
| IS THE BATH CIRCUIT ON TEH PLAN. |
| |
| 5} AHU #1 IS NOT LISTED ON THE SCHEDULE. |
| |
| 6} A/C COMPRESSER #1 IS NOT LISTED AND |
| HAS THE WRONG CIRCUIT NUMBERS AT THE |
| UNIT ON THE PLAN. |
| |
| 7} PER 210.12 CIRCUIT G5 (SMOKE |
| DETECTORS) MUST BE ON A AFCI. THEY |
| CANNOT BE ON THE BATHROOM CIRCUIT, SEE |
| 210.11(C)(3). |
| |
| 8} THE INITIALS ON THE ARCHITECTS SEAL |
| IS NOT THE SAME AS THE "SIGNATURE" ON |
| THE SEAL DATED 8/13/04. THE ARCHITECT |
| MUST SIGN HIS SEAL PER 61G1-16.003 |
| FLORIDA ADMINISTRATIVE CODE. ONE SET OF |
| PLANS IS BEING RETAINED BY THIS OFFICE |
| WITH THIS APPARANTLY UNAUTHORIZED " |
| SIGNATURE". |
| |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |