2006-07-10 00:00:00 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE REVISED PLAN SHOWS AN EXISTING |
| SERVICE THAT DOES NOT CORRELATE WITH THE |
| "EXISTING SERVICE" SUBMITTED ON THE |
| ORIGINAL PLAN. THIS WILL BE REVIEWED AS |
| A NEW SERVICE, AND THE FOLLOWING |
| COMMENTS APPLY. |
| A)PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| B) THE GROUNDING ELECTRODE MUST COMPLY |
| WITH THE MINIMUM SIZE FOR THE SERVICE |
| PER 250.66. |
| C) THE RISER INDICATES THE MAINS IN THE |
| PANELS, THE PLAN SHOWS A MAIN DISCONNECT |
| AT THE METER. PLEASE INDICATE PROPOSED |
| INTENTION. |
| D) ALL AVAILABLE ELECTRODES MUST BE |
| BONDED PER 250.50. |
| |
| 2} INDICATE THE LOCATION OF THE PANELS |
| ON THE PLAN. |
| |
| 3} THE RISER SHOWS PANEL "A" FEEDING |
| PANEL "G", BUT NOT SHOWN ON THE PANEL |
| SCHEDULE.INDICATE FEEDER AND OCP SIZE IN |
| THE SCHEDULE. |
| |
| 4} THE CIRCUIT NUMBERS DESIGNATIONS ARE |
| DUPLICATED IN BOTH PANELS. PLEASE USE |
| PANEL DESIGNATION (1A)FOR CIRCUIT #1 |
| PANEL "A". |
| |
| 5} CIRCUIT 17B AND 19A HAS AN INCORRECT |
| OCP (25 AMPS), AND WIRE SIZE(#10) FOR |
| THE 10300 WATT LOAD. 310.16. |
| |
| 6} CIRCUITS 1 AND 3, PANEL "G", SAME |
| COMMENT AS #5. |
| |
| 7} THE WIRE SIZE IS TOO SMALL SMALL FOR |
| THE LOAD AND OCP, CIRCUIT 2 &4, PANEL |
| "G". 310.16. |
| |
| 8} CIRCUIT #2A, PANEL"A", BATH#2 MUST |
| COMPLY WITH 210.11(C)(3), IF SERVING THE |
| RECEPTACLE. |
| |
| 9) THE ELECTRICAL NOTES INDICATE A |
| MINIMUM WIRE SIZE OF #12, BUT #14 IS |
| SHOWN ON THE PANEL SCHEDULE IN SEVERAL |
| PLACES. PLEASE ADJUST THE NOTE OR CHANGE |
| THE SCHEDULE TO REFLECT THE NOTE. THIS |
| IS THE SECOND TIME THIS COMMENT HAS BEEN |
| MADE. |
| |
| 10} NOTE 24 IS CODE COMPLIANT AS LONG AS |
| THE CIRCUIT IS AFCI PROTECTED PER |
| 210.12. |
| |
| 11} SMOKE DETECTORS ARE REQUIRED PER |
| 313.1 FBC. |
| |
| 12} RECEPTACLES ARE REQUIRED WITHIN 25' |
| OF THE CONDENSING UNITS PER 210.63. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |