2006-07-10 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE REVISED PLAN SHOWS AN EXISTING
 SERVICE THAT DOES NOT CORRELATE WITH THE
 "EXISTING SERVICE" SUBMITTED ON THE
 ORIGINAL PLAN. THIS WILL BE REVIEWED AS
 A NEW SERVICE, AND THE FOLLOWING
 COMMENTS APPLY.
 A)PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
 B) THE GROUNDING ELECTRODE MUST COMPLY
 WITH THE MINIMUM SIZE FOR THE SERVICE
 PER 250.66.
 C) THE RISER INDICATES THE MAINS IN THE
 PANELS, THE PLAN SHOWS A MAIN DISCONNECT
 AT THE METER. PLEASE INDICATE PROPOSED
 INTENTION.
 D) ALL AVAILABLE ELECTRODES MUST BE
 BONDED PER 250.50.
  
 2} INDICATE THE LOCATION OF THE PANELS
 ON THE PLAN.
  
 3} THE RISER SHOWS PANEL "A" FEEDING
 PANEL "G", BUT NOT SHOWN ON THE PANEL
 SCHEDULE.INDICATE FEEDER AND OCP SIZE IN
 THE SCHEDULE.
  
 4} THE CIRCUIT NUMBERS DESIGNATIONS ARE
 DUPLICATED IN BOTH PANELS. PLEASE USE
 PANEL DESIGNATION (1A)FOR CIRCUIT #1
 PANEL "A".
  
 5} CIRCUIT 17B AND 19A HAS AN INCORRECT
 OCP (25 AMPS), AND WIRE SIZE(#10) FOR
 THE 10300 WATT LOAD. 310.16.
  
 6} CIRCUITS 1 AND 3, PANEL "G", SAME
 COMMENT AS #5.
  
 7} THE WIRE SIZE IS TOO SMALL SMALL FOR
 THE LOAD AND OCP, CIRCUIT 2 &4, PANEL
 "G". 310.16.
  
 8} CIRCUIT #2A, PANEL"A", BATH#2 MUST
 COMPLY WITH 210.11(C)(3), IF SERVING THE
 RECEPTACLE.
  
 9) THE ELECTRICAL NOTES INDICATE A
 MINIMUM WIRE SIZE OF #12, BUT #14 IS
 SHOWN ON THE PANEL SCHEDULE IN SEVERAL
 PLACES. PLEASE ADJUST THE NOTE OR CHANGE
 THE SCHEDULE TO REFLECT THE NOTE. THIS
 IS THE SECOND TIME THIS COMMENT HAS BEEN
 MADE.
  
 10} NOTE 24 IS CODE COMPLIANT AS LONG AS
 THE CIRCUIT IS AFCI PROTECTED PER
 210.12.
  
 11} SMOKE DETECTORS ARE REQUIRED PER
 313.1 FBC.
  
 12} RECEPTACLES ARE REQUIRED WITHIN 25'
 OF THE CONDENSING UNITS PER 210.63.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  