Plan Review Notes
Plan Review Notes For Permit 04070958
Permit Number 04070958
Review Stop E
Sequence Number 2
Notes
Date Text
2004-09-16 00:00:00***** NOTES REDLINED ****
  
 BATH CIRCUIT STILL SHOWN AS #14/15AMP
 CIRCUIT. PLEASE SEE 210.52D/210.11C3
  
 NOTE MENTIONS ALL WIRING TO BE MIN #12
 AND YET PANEL SCHEDULE INDICATES #14 FOR
 MANY CIRCUITS.
  
 SD'S TO NOTED TO BE ON BATH/KITCHEN LTS
 PLEASE SEE "ALL OUTLETS" IN 210.12 2002
 NEC. THIS INCLUDES SD'S.
  
  
 ** PLEASE SEE SD'D REQUIRED IN EXISTING
 BEDRMS.
  
  
  
 **REVISE BEFORE ROUGH. ***