Plan Review Notes For Permit 04070958 |
Permit Number |
04070958 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-09-16 00:00:00 | ***** NOTES REDLINED **** | | | | BATH CIRCUIT STILL SHOWN AS #14/15AMP | | CIRCUIT. PLEASE SEE 210.52D/210.11C3 | | | | NOTE MENTIONS ALL WIRING TO BE MIN #12 | | AND YET PANEL SCHEDULE INDICATES #14 FOR | | MANY CIRCUITS. | | | | SD'S TO NOTED TO BE ON BATH/KITCHEN LTS | | PLEASE SEE "ALL OUTLETS" IN 210.12 2002 | | NEC. THIS INCLUDES SD'S. | | | | | | ** PLEASE SEE SD'D REQUIRED IN EXISTING | | BEDRMS. | | | | | | | | **REVISE BEFORE ROUGH. *** |
|