2004-07-28 00:00:00 | | | THE PANEL SCHEDULE SHOWS EXISTING | | CIRCUITS AND THE DRAWING IS SHOWING NEW | | CIRCUITS. PLEASE CORRELATE WHAT IS | | BEING ADDED OR CHANGED. | | THE CIRCUIT NUMBERS ON THE PANEL | | SCHEDULE DO NOT MATCH THE NUMBERS ON | | THE DRAWINGS IN THE KITCHEN. IS THIS | | NEW OR EXISTING WORK? | | | | PLEASE CLARIFY THE SCOPE AND CORRELATE | | THE DRAWINGS. ALSO SEE HIGHLIGHTED | | NOTES ON SHEET E-1-0 ARE QUOTING OUT | | DATED CODES. | | | | PLEASE NOTE THAT THE ARCHITECTS | | SIGNATURE IS REQUIRED ON HIS/HER SEAL | | PER 61G116.003.INITIALS ARE NOT | | ACCEPTABLE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|