Plan Review Notes For Permit 04070859 |
Permit Number |
04070859 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-29 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE LIST ALL THE REQUIRED | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | SCHEDULE PER 210.11C3. | | | | 2} PLEASE LIST THE REQUIRED ARC | | FAULT PROTECTED CIRCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | 3} A RECEPTACLE IS REQUIRED IN BEDROOM | | #4 PER 210.52(A)(1). | | | | 4} PLEASE SEE MISSING RECEPT REQUIRED | | FOR A/C EQUIPMENT PER 210.63. | | | | 5} THE DISCONNECTS FOR THE CONDENSING | | UNITS ARE NOT IN CLEARANCE REQUIREMENTS | | OF ATRICLE 110.26. | | | | ALL INFORMATION/DRAWINGS/SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON | | RESPON-SIBLE FOR THE DESIGN. SECTION | | 104.2.1. | | SEE ELECTRICAL PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|