Plan Review Notes
Plan Review Notes For Permit 04070859
Permit Number 04070859
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-29 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE PER 210.11C3.
  
 2} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 3} A RECEPTACLE IS REQUIRED IN BEDROOM
 #4 PER 210.52(A)(1).
  
 4} PLEASE SEE MISSING RECEPT REQUIRED
 FOR A/C EQUIPMENT PER 210.63.
  
 5} THE DISCONNECTS FOR THE CONDENSING
 UNITS ARE NOT IN CLEARANCE REQUIREMENTS
 OF ATRICLE 110.26.
  
 ALL INFORMATION/DRAWINGS/SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPON-SIBLE FOR THE DESIGN. SECTION
 104.2.1.
 SEE ELECTRICAL PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved