2004-08-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| |
| |
| A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| FORMATION REQUIRED FOR PLAN REVIEW |
| 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE |
| WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| 2) FBC-2001424.2.6.6.5 WHERE PROVIDED, |
| THE VACUUM OR PRESSURE CLEANER FITTING |
| SHALL BE LOCATED AT LEAST 6" AND NOT |
| GREATER THAN 12" BELOW THE MINIMUM OPER- |
| ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| THE SKIMMER. |
| 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| ORD. #2853-95, BACKFLOW REQUIRED ON |
| WATER SERVICE. (ADD TO NOTES) |
| 4) FBC-2001 424.2.12.1 PRESSURE TESTS. |
| PER MANUFACTURE RECOMMENDATIONS, NO AIR |
| TEST SHALL BE APPROVED FOR PVC PIPE AND |
| FITTINGS. (ADD TO NOTES) |
| 5) FBC-2001 424.2.13.2JOINTS AND CON- |
| NECTIONS, FBC PLMG SEC 605.21, PURPLE |
| PRIMER REQUIRED ON PVC PIPING. (ADD TO |
| NOTES) |
| 6) FBC02001 424.2.15 GAS PIPING SHALL |
| COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| AND PERMIT REQUIRED. |
| 7) EXTERNAL HARTFORD LOOP REQUIRED. NO |
| INTERNAL MEANS OF WATER RETENTION IS |
| SHOWN. SECTION 424.2.14.2 |
| |