Plan Review Notes
Plan Review Notes For Permit 04070744
Permit Number 04070744
Review Stop E
Sequence Number 1
Notes
Date Text
2004-07-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SPECIFY THE SERVICE BEING USED IN
 PLACE OF THE GENERIC ONE ON THE RISER
 DIAGRAM.
  
 2} VERIFY THE PANEL IN THE PANTRY
 COMPLIES WITH 110.26 CLEARANCE
 REQUIREMENTS.
  
 3} NOTE THE DISCONNECT LOCATION ON THE
 PLAN IF REQUIRED BY 230.70 CWPB
 AMMENDMENTS.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110.9.
  
 5} PLEASE LIST ALL THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.11C3
  
 6} PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 7} RECEPTACLES ARE REQUIRED ON THE
 KITCHEN ISLAND PER210.52(C)(2), AND GFI
 PER 210.8(A)(6).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026