Plan Review Notes For Permit 04070744 |
Permit Number |
04070744 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-22 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SPECIFY THE SERVICE BEING USED IN | | PLACE OF THE GENERIC ONE ON THE RISER | | DIAGRAM. | | | | 2} VERIFY THE PANEL IN THE PANTRY | | COMPLIES WITH 110.26 CLEARANCE | | REQUIREMENTS. | | | | 3} NOTE THE DISCONNECT LOCATION ON THE | | PLAN IF REQUIRED BY 230.70 CWPB | | AMMENDMENTS. | | | | 4} PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW SERVICE EQUIPMENT BEING | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | CURRENT PER 110.9. | | | | 5} PLEASE LIST ALL THE REQUIRED | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | SCHEDULE. PER 210.11C3 | | | | 6} PLEASE LIST THE REQUIRED ARC | | FAULT PROTECTED CIRCUIT(S) ON PANEL | | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" | | IN BEDROOMS ARE TO BE PROTECTED , | | INCLUDING, LTS, RECEPTS, SD'S ETC. | | | | 7} RECEPTACLES ARE REQUIRED ON THE | | KITCHEN ISLAND PER210.52(C)(2), AND GFI | | PER 210.8(A)(6). | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|