Plan Review Notes
Plan Review Notes For Permit 04070734
Permit Number 04070734
Review Stop M
Sequence Number 1
Notes
Date Text
2004-07-26 00:00:00PROVISO:
 PER THE REVISED 2001 FBC(M) 601.4,
 RETURN AIR IS TO BE EQUAL TO THE SUPPLY
 AIR INTO THAT SPACE.EXCEPTION #3, ALL
 AIR INTO THE MASTER SUITE IS TO BE
 INCLUDED.
  
 RETURN AIR FROM THE MASTER SUITE SHALL
 BE A MINIMUM OF 12".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.