Plan Review Notes For Permit 04070734 |
Permit Number |
04070734 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-07-21 00:00:00 | ************ UNSAT ***************** | | | | 1)NOTE: PLEASE SEE FBC WHICH REQUIRES | | THE PRINTED NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR PLANS. | | 104.2.1 | | | | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | WITH LOAD CALCULATIONS. PLEASE SEE POOL | | HEATER SHOWN ON LOAD CALCS BUT NOT | | PANEL? | | PLEASE ALSO SEE OCP AND AWG FOR WHAT IS | | SHOWN AS POOL EQUIPMENT? PLEASE CLARIFY | | EQUIPMENT. PUMP? 1.5KW LOAD SHOWN. | | | | 3)NOTE: PLEASE SEE MISSING RECEPT PER | | 210.52 IN MAST SUITE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|