Plan Review Notes For Permit 04070644
Permit Number 04070644
Review Stop M
Sequence Number 1
Notes
Date Text
2004-07-16 00:00:00DENIED:
 TRANSFER GRILLE FROM THE MASTER BEDROOM
 IS NOT SIZED PROPERLY.PER THE REVISED
 2001 FBC(M) 601.4 EXCEPTION #2 & 3,
 TRANSFER GRILLES SHALL BE 50 SQ INCHES
 OF OPEN AREA TO 100 CFM OF SUPPLY AIR.
 ALL THE AIR INTO THE MASTER SUITE IS TO
 BE INCLUDED FOR A TOTAL OF SUPPLY AIR
 TO THAT SPACE.PLAN INDICATES A TOTAL
 OF 210 CFMFOR THE SUPPLY.RETURN AIR
 SHALL BE A MINIMUM OF 12" X 10".
  
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  