1 |
|
Notes |
Date |
Text |
2004-07-16 00:00:00 | DENIED: | | TRANSFER GRILLE FROM THE MASTER BEDROOM | | IS NOT SIZED PROPERLY.PER THE REVISED | | 2001 FBC(M) 601.4 EXCEPTION #2 & 3, | | TRANSFER GRILLES SHALL BE 50 SQ INCHES | | OF OPEN AREA TO 100 CFM OF SUPPLY AIR. | | ALL THE AIR INTO THE MASTER SUITE IS TO | | BE INCLUDED FOR A TOTAL OF SUPPLY AIR | | TO THAT SPACE.PLAN INDICATES A TOTAL | | OF 210 CFMFOR THE SUPPLY.RETURN AIR | | SHALL BE A MINIMUM OF 12" X 10". | | | | AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 FBC(M) | | 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|