2004-07-19 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND RISER DIAGRAM.
 PANEL SCHEDULE IS SHOWN AS 42 CIR, 200A
 PANEL 10PL, YET RISER SHOWS A 60A SUB-
 -FEED TO A PANEL 24CIR PANEL "GH"??
  
 2)NOTE: PLEASE SEE EQUIPMENT AS SHOWN
 ON RISER BEING CONNECTED TO PANEL IS
 NOT LISTED ON SUBMITTED PANEL SCHEDULE.
  
 3)NOTE: PLEASE SEE POWER/COMM PLAN.
 NOTE SAYS: "NOW WORKING KITCHEN UNIT"
 DISPLAY ONLY. ?? PLEASE CLARIFY.
  