2004-08-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS.
 A) KITCHEN SINK SHALL NOT DRAIN INTO
 THE WET VENT FOR THE BATHROOM. SECTION
 909.1- THE KITCHEN SINK SHALL DISCHAR-
 GE DOWNSTREAM OF THE BATHROOM FIXTURES.
 B) THE WASH MACHINE SHALL NOT DRAIN IN-
 TO THE WET VENT FOR THE BATHROOM. SECT-
 ION 909.1. - THE WASH MACHINE SHALL DIS-
 CHARGE DOWNSTREAM OF THE BATHROOM FIXTU-
 RES.
 C) THE BATHROOM FROM THE SECOND FLOOR
 SHALL NOT DRAIN PAST THE KITCHEN SINK.
 SECTION 908.3
 2) ALL INFORMATION, DRAWINGS, SPECIFIC-
 ATIONS AND ACCOMPANYING DATA SHALL BEAR
 THE NAME AND SIGNATURE OF THE PERSON RE-
 SPONSIBLE FOR THE DESIGN.
  