Plan Review Notes For Permit 04070616 |
Permit Number |
04070616 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-08-02 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1) SANITARY RISER DIAGRAM DOES NOT MEET | | CODE REQUIREMENTS. | | A) KITCHEN SINK SHALL NOT DRAIN INTO | | THE WET VENT FOR THE BATHROOM. SECTION | | 909.1- THE KITCHEN SINK SHALL DISCHAR- | | GE DOWNSTREAM OF THE BATHROOM FIXTURES. | | B) THE WASH MACHINE SHALL NOT DRAIN IN- | | TO THE WET VENT FOR THE BATHROOM. SECT- | | ION 909.1. - THE WASH MACHINE SHALL DIS- | | CHARGE DOWNSTREAM OF THE BATHROOM FIXTU- | | RES. | | C) THE BATHROOM FROM THE SECOND FLOOR | | SHALL NOT DRAIN PAST THE KITCHEN SINK. | | SECTION 908.3 | | 2) ALL INFORMATION, DRAWINGS, SPECIFIC- | | ATIONS AND ACCOMPANYING DATA SHALL BEAR | | THE NAME AND SIGNATURE OF THE PERSON RE- | | SPONSIBLE FOR THE DESIGN. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|