2004-09-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW
 SHT P-2 FLOOR DRAIN AT WATER HEATER AND
 IN KITCHEN NOT APPROVED FOR INDIRECT
 WASTE. INDICATE THE USE OF THE FLOOR
 DRAIN IN THE KITCHEN. WHAT IS DRAINING
 INTO THE FLOOR DRAIN? - THE WATER HEATER
 SHALL DRAIN INTO A FLOOR SINK OR A HUB
 DRAIN. SECTIONS 802.3 OR 802.3.2
  
 SHT P-2 WATER HAMMER ARRESTORS ARE RE-
 QUIRED AT THE DISH WASHER, ICE MAKER, &
 WASH MACHINE. SECTION 604.9. SHOW ON THE
 WATER RISER DIAGRAM.
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) & 471.025.
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
  
 **************NEW COMMENT***************
 THE RESIDENTIAL UNIT ON THE SECOND FLOOR
 SHALL HAVE IT'S OWN WATER SERVICE WITH A
 SHUT OFF VALVE THAT IS ACCESSIBLE. IT IS
 SHOWN TIED INTO THE DISTRIBUTION LINES
 OF THE LOWER UNIT WHICH IS NOT ACCEPT-
 ABLE. SECTION 606.1(5).
  
 REVIEW BY KEN STEVENS