Plan Review Notes
Plan Review Notes For Permit 04070599
Permit Number 04070599
Review Stop E
Sequence Number 3
Notes
Date Text
2004-09-21 00:00:00************ UNSAT *****************
  
 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 PLEASE ALSO SEE 210.52C1-5 FOR REQUIRED
 RECEPTS/SPACING.
  
 2) NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE UNIT HAS BEEN CONVERTED FROM
 COMMERICAL TO RESIDENTIAL USE.
 RECEPT SPACING TO MEET ABOVE.
  
 3 )NOTE: PLEASE SEE MISSING REQ'D EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210.70 AND LS-101 5-8
 PLEASE SEE EXITING INTO HALLWAY FROM
 UNIT. APPEARS TO TURN ON A LT OUTSIDE
 BUT NOT IN HALL.
  
 4)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 210.12 2002 NEC.
  
 5)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM
 IS BEING SHOWN ON FIRST FLOOR AND ALSO
 INSIDE RESIDENTIAL UNIT.
 THIS INDICATES ELECTRICAL IN THIS ROOM
 FEEDING UPSTAIRS RESIDENTIAL UNIT.\
 THIS IS NOT PERMITTED.
 UPSTAIRS RESIDENT MUST HAVE ACCESS TO
 MEANS OF DISCONNECT FOR HIS/HER OWN
 RESIDENTIAL UNIT W/OUT ENTERING THE
 RESIDENCE OF ANOTHER.
 230.70,225.31,225.32,2255.35 ETC.
 THIS ROOM WOULD BE REQUIRED TO BUILT
 SEPARATE FROM EACH UNIT WITH A MIN OF
 1-HOUR RATING.
 PLEASE ALSO SEE 230.72 FOR GROUPING OF
 MAINS TO BLDG.
  
 6)NOTE: PLEASE SEE EXISTING GARAGE IS
 REQUIRED TO SHOW EITHER NEW ELECTRICAL
 OR EXISITNG ELECTRICAL TO MEET 2002 NEC.
 PLEASE ALSO SEE FBC CHAPTER 34 3401.7.2-
 .6.
 PLEASE ALSO SEE DUE TO CHANGE IN
 OCCUPANCY, MUST ALSO BE BROUGHT UP TO
 CODE.
  
 7)NOTE: PLEASE SEE 210.52D WHICH REQUIRE
 -S A GFI RECEPT A MAX OF 3' FROM SINK/
 LAVS IN BATH RMS.
  
 8)NOTE: PLEASE SEE WALK-IN CLOSET WHICH
 SHOWS AHU AND WATER HEATER. PLEASE SEE
 110.26 FOR MIN CLEARENCE FOR DISC MEANS.
 PLEASE ALSO SEE 422.17 FOR WATER HEATER.
  
 9 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 10)NOTE: PLEASE VERIFY 7.2KW SHOWN FOR
 AHU'S FOR FIRST FLR LOAD CALCUALTIONS.??
 PLEASE SEE ALL AHU LOADS ON PANEL SCHED-
 -ULES. THESE DO NOT SEEM TO CORRELATE.
 PLEASE ALSO SEE 220.31B FOR FIGURING
 HEAT LOAD OF AHU'S.
  
 11)NOTE: PLEASE SEE TWO "EXISTING" DISC
 "C"??
 PLEASE CORRELATE AND LABEL ACCORD.
 230.2E
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWER-
 (S) WHICH MAY AFFECT ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]