2004-09-21 00:00:00 | ************ UNSAT ***************** |
| |
| 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| PLEASE ALSO SEE 210.52C1-5 FOR REQUIRED |
| RECEPTS/SPACING. |
| |
| 2) NOTE: PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12` RULE. |
| PLEASE SEE UNIT HAS BEEN CONVERTED FROM |
| COMMERICAL TO RESIDENTIAL USE. |
| RECEPT SPACING TO MEET ABOVE. |
| |
| 3 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| PER 210.70 AND LS-101 5-8 |
| PLEASE SEE EXITING INTO HALLWAY FROM |
| UNIT. APPEARS TO TURN ON A LT OUTSIDE |
| BUT NOT IN HALL. |
| |
| 4)NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| 210.12 2002 NEC. |
| |
| 5)NOTE: PLEASE SEE MAIN ELECTRICAL ROOM |
| IS BEING SHOWN ON FIRST FLOOR AND ALSO |
| INSIDE RESIDENTIAL UNIT. |
| THIS INDICATES ELECTRICAL IN THIS ROOM |
| FEEDING UPSTAIRS RESIDENTIAL UNIT.\ |
| THIS IS NOT PERMITTED. |
| UPSTAIRS RESIDENT MUST HAVE ACCESS TO |
| MEANS OF DISCONNECT FOR HIS/HER OWN |
| RESIDENTIAL UNIT W/OUT ENTERING THE |
| RESIDENCE OF ANOTHER. |
| 230.70,225.31,225.32,2255.35 ETC. |
| THIS ROOM WOULD BE REQUIRED TO BUILT |
| SEPARATE FROM EACH UNIT WITH A MIN OF |
| 1-HOUR RATING. |
| PLEASE ALSO SEE 230.72 FOR GROUPING OF |
| MAINS TO BLDG. |
| |
| 6)NOTE: PLEASE SEE EXISTING GARAGE IS |
| REQUIRED TO SHOW EITHER NEW ELECTRICAL |
| OR EXISITNG ELECTRICAL TO MEET 2002 NEC. |
| PLEASE ALSO SEE FBC CHAPTER 34 3401.7.2- |
| .6. |
| PLEASE ALSO SEE DUE TO CHANGE IN |
| OCCUPANCY, MUST ALSO BE BROUGHT UP TO |
| CODE. |
| |
| 7)NOTE: PLEASE SEE 210.52D WHICH REQUIRE |
| -S A GFI RECEPT A MAX OF 3' FROM SINK/ |
| LAVS IN BATH RMS. |
| |
| 8)NOTE: PLEASE SEE WALK-IN CLOSET WHICH |
| SHOWS AHU AND WATER HEATER. PLEASE SEE |
| 110.26 FOR MIN CLEARENCE FOR DISC MEANS. |
| PLEASE ALSO SEE 422.17 FOR WATER HEATER. |
| |
| 9 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| |
| 10)NOTE: PLEASE VERIFY 7.2KW SHOWN FOR |
| AHU'S FOR FIRST FLR LOAD CALCUALTIONS.?? |
| PLEASE SEE ALL AHU LOADS ON PANEL SCHED- |
| -ULES. THESE DO NOT SEEM TO CORRELATE. |
| PLEASE ALSO SEE 220.31B FOR FIGURING |
| HEAT LOAD OF AHU'S. |
| |
| 11)NOTE: PLEASE SEE TWO "EXISTING" DISC |
| "C"?? |
| PLEASE CORRELATE AND LABEL ACCORD. |
| 230.2E |
| |
| PLEASE SEE COMMENTS FROM OTHER REVIEWER- |
| (S) WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| INSERT NEW SHEETS INTO TWO COMPLETE SETS |
| FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |