Plan Review Notes
Plan Review Notes For Permit 04070574
Permit Number 04070574
Review Stop B
Sequence Number 1
Notes
Date Text
2004-07-23 00:00:00NO SKYLIGHT PRODUCT APPROVAL SUBMITTED
 FOR WIND.
 CALLED SKYLIGHT CONCEPTS FAXED LOCAL
 APPROVAL WILL HOLD PLANS UNTIL 7/26/04
 PM TO SEE IF THEY FAX INFOR.
 7/27/04 INFO FAXED FROM CATALFUMO,
 CHART WITH A SUMMARY OF PRESSURES
 TESTED, NO ACTUAL TEST REPORT!!!CALLED
 GOODY AND JOHN EXPLAINED WE NEED A TEST
 REPORT, WHAT DO THEY WANT TO DO, REMOVE
 SKYLIGHTS FROM REPORT OR NEW INFO?
 7/30/04 RECEIVED A LETTER FROM WASCO
 SKYLIGHT SYSTEMS STATING MODEL CA SINGLE
 DOME SKYLIGHT WAS TESTED TO 125 MPH
 SUSTAINED WIND/ (EQUALLS 145 3 SEC GUST)
 NO TESTING REPORT SUBMITTED, NO INFORMA-
 TION FOR LOCAL PRODUCT APPROVAL, NO
 THIRD PARTY QUALITY ASSURANCE ENTITY
 APPROVED BY STATE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026