Date |
Text |
2004-07-30 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FBC-2001 BUILDING |
| |
| 1) SHT A-4.0 SUBMIT CALCULATIONS FOR |
| ROOF SCUPPERS. SHOW SQUARE FOOTAGE FOR |
| EACH AREA OF ROOF AND SHOW 1/2 AREA OF |
| VERTICAL WALLS INCLUDING PARAPETS AS ITS |
| ADDED TO ROOF AREA. INDICATE TOTAL SF |
| FOR EACH DRAIN. LOWER ROOF CALCULATIONS |
| ALSO. SECTIONS 1106 & 1107 AND ALL SUB- |
| SECTIONS. - SCUPPER DRAIN SHALL BE SIZED |
| LARGE ENOUGH TO FOR PRIMARY AND SECOND- |
| ARY DRAINS. |
| 2) SHT A-7.0 COFFEE AREA SINK, A CLEAR |
| FLOOR SPACE SHALL BE PROVIDED IN FRONT |
| OF THE SINK TO ALLOW FORWARD APPROACH |
| MAXIMUM OF 19" UNDER THE SINK. - ALSO |
| PER THE BLDG OFFICIAL CABINET DOORS AT |
| CLEAR SPACE CREATE A HARDSHIP AND SHALL |
| NOT BE INSTALLED. SECTION 11-4.24.5 - |
| ALSO SHOW KNEE CLEARANCE SECTION 4.24.3. |
| 3) SECTION 11-4.24.4 SINK DEPTH SHALL BE |
| A MAXIMUM OF 6-1/2" DEEP. SINK REFERENC- |
| ED ON SHEET M-1 FIXTURE SCHEDULE (3), |
| SHOWS ELKAY MODEL ECC-2522. DEPTH OF |
| THIS SINK IS 7-1/2" AS SHOWN ON ATTACHED |
| SHEET. |
| 4) SUBMIT A DETAIL SHOWING COMPLIANCE |
| WITH SECTION 11-4.15 AND ALL SUBSECTIONS |
| (DRINKING FOUNTAIN) |
| 5) 1204.2 SURROUNDING MATERIALS; |
| THE WALLS & FLOORS OF ALL PUBLIC REST- |
| ROOMS SHALL BE LINED WITH NONABSORBANT |
| MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| FLOOR. - NOTE: SHT A-8.0 INDICATES LATEX |
| PAINT. THIS IS NOT ACCEPTABLE AS A NON- |
| ABSORBANT MATERIAL. |
| 6) SHT M-1 PLUMBING NOTES #10, AIR CHAM- |
| BERS ARE NOT APPROVED. DELETE REFERENCE |
| FROM NOTES. SECTION 104.2.1 |
| 7) SEPARATE IRRIGATION PLANS AND PERMIT |
| ARE REQUIRED. SECTION 1-4.3.1.1 |
| 8) SECTION 607.3.1 THERMAL EXPANSION |
| CONTROL IS REQUIRED. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |