Plan Review Notes
Plan Review Notes For Permit 04070546
Permit Number 04070546
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
  
 1) SHT A-4.0 SUBMIT CALCULATIONS FOR
 ROOF SCUPPERS. SHOW SQUARE FOOTAGE FOR
 EACH AREA OF ROOF AND SHOW 1/2 AREA OF
 VERTICAL WALLS INCLUDING PARAPETS AS ITS
 ADDED TO ROOF AREA. INDICATE TOTAL SF
 FOR EACH DRAIN. LOWER ROOF CALCULATIONS
 ALSO. SECTIONS 1106 & 1107 AND ALL SUB-
 SECTIONS. - SCUPPER DRAIN SHALL BE SIZED
 LARGE ENOUGH TO FOR PRIMARY AND SECOND-
 ARY DRAINS.
 2) SHT A-7.0 COFFEE AREA SINK, A CLEAR
 FLOOR SPACE SHALL BE PROVIDED IN FRONT
 OF THE SINK TO ALLOW FORWARD APPROACH
 MAXIMUM OF 19" UNDER THE SINK. - ALSO
 PER THE BLDG OFFICIAL CABINET DOORS AT
 CLEAR SPACE CREATE A HARDSHIP AND SHALL
 NOT BE INSTALLED. SECTION 11-4.24.5 -
 ALSO SHOW KNEE CLEARANCE SECTION 4.24.3.
 3) SECTION 11-4.24.4 SINK DEPTH SHALL BE
 A MAXIMUM OF 6-1/2" DEEP. SINK REFERENC-
 ED ON SHEET M-1 FIXTURE SCHEDULE (3),
 SHOWS ELKAY MODEL ECC-2522. DEPTH OF
 THIS SINK IS 7-1/2" AS SHOWN ON ATTACHED
 SHEET.
 4) SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 (DRINKING FOUNTAIN)
 5) 1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR. - NOTE: SHT A-8.0 INDICATES LATEX
 PAINT. THIS IS NOT ACCEPTABLE AS A NON-
 ABSORBANT MATERIAL.
 6) SHT M-1 PLUMBING NOTES #10, AIR CHAM-
 BERS ARE NOT APPROVED. DELETE REFERENCE
 FROM NOTES. SECTION 104.2.1
 7) SEPARATE IRRIGATION PLANS AND PERMIT
 ARE REQUIRED. SECTION 1-4.3.1.1
 8) SECTION 607.3.1 THERMAL EXPANSION
 CONTROL IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]